Cable duct and fan subassemblies
9.5 The 24 V DC fan subassembly (6ES7408-1TA01-0XA0)
S7-400 Automation System Module Data
402 Reference Manual, Edition 09/2009, A5E00850736-06
CAUTION
Danger of damage to equipment.
If you insert the monitoring PCB in the wrong position in the fan subassembly, the fan
subassembly may be damaged.
During maintenance of the unit, make sure you do not insert the replacement monitoring
PCB in the wrong position.
Monitoring function
In the case of a fault (defective fans) the fans are not switched off. Once you have replaced
the defective fan(s), the fault is acknowledged automatically as soon as the fans have
reached the required speed. Any faults that occur are not stored.
When you switch on the fan subassembly, the fans start running. After approximately 10 s
the current status of the fans is indicated via LEDs and relays.