Technical Data
4
SPC6000
23
Siemens AB
A6V10276959
Security Products
18.11.2011
Dimensions (W x H x D)
SPC5320: 264 x 357 x 81 mm
SPC5330: 326 x 415 x 114 mm
Housing
SPC5320: Small metal housing SPC5330: Hinged metal
housing,
(1.2 mm mild steel)
Housing can contain up to
SPC5320: 1 additional expander,
SPC5330: 4 additional expanders (size 150 mm x 82 mm)
1) Max. 400 m between devices / cable types IYSTY 2 x 2 x Ø 0.6 mm (min.), UTP
cat5 (solid core) or Belden 9829.
2) More I/O expanders can be addressed instead of a keypad or door expander,
but number of programmable inputs / outputs cannot exceed specified system
limits.
4.3 SPC6000
Programmable areas
60
Max. number of user codes
512
Remote controls
Up to 512 (1 per user)
Wireless Panic Alarm
Up to 120
Event memory
10'000 intrusion events, 10'000 access events
Number of on-board zones
8
Max. number of hardwired
zones
512
Max. number of wireless
zones
120 (take away wired zones)
EOL resistor
Dual 4k7 (default), other resistor combinations configurable
Number of on-board relays
1 strobe (30 VDC / 1 A resistive switching current)
Number of on-board open
coll.
2 internal / external bell, 3 freely programmable (each max.
400 mA resistive switching current, supplied via auxiliary
output)
Firmware
V3.x
Door capacity
Max. 64 entry doors or 32 entry/exit doors
Number of card reader
Max. 64
Radio module
Optional (SPCW110)
Verification
16 verification zones with max. 4 IP-cameras and 16 audio
devices.
Video
Up to 16 pre / 16 post event images (by JPEG resolution
320 x 240, max. 1 frame / sec.)