Siemens Protection Devices Limited 4
46BC Phase Unbalance/Broken Conductor
Element has settings for pickup level and DTL delay. With
the circuit breaker closed, if the NPS:PPS current ratio is
above setting this could be due to a broken conductor.
50BF Circuit Breaker Fail
The circuit breaker fail function may be triggered from an
internal trip signal or from a binary input. Line currents
and earth currents are monitored following a trip signal
and an output is issued if any current is still detected,
above setting, after a specified time interval.
Alternatively, if the trip is from a mechanical protection
the circuit breaker position can be used to determine a
failure. A second time delay is available to enable another
stage to be utilized if required. An input is also available
to bypass the time delays when the circuit breaker is
known to be faulty.
50/51 Phase Fault
50 INST/DTL and 51 IDMTL/DTL elements provide
overcurrent protection, each with independent settings
for pickup current, time-multiplier (51) and time-delays.
User can select IEC or ANSI time current characteristics.
The IDMT stage has a user programmable reset
characteristic, either DTL or shaped current ~ time reset
characteristic, to improve grading with electromechanical
protection.
50G/51G/50N/51N Earth Fault/ Earth Fault
Two earth fault measurement modes are available. One
mode directly measures the earth current from an
independent CT, or the residual connection of the 3 line
CTs. This input can be ordered as either earth fault or
sensitive earth fault (50G/51G).
The second mode derives the earth current internally
from the 3 phase CT inputs to give earth fault (50N/51N).
50 INST/DTL and 51 IDMTL/DTL elements provide
overcurrent protection, each with independent settings
for pickup current, time-multiplier (51) and time-delays.
User can select IEC or ANSI time current characteristics.
The IDMT stage has a user programmable reset
characteristic either DTL or shaped current ~ time reset
characteristic to improve grading with electromechanical
protection.
0.1
1
10
100
1000
110
Current (multiples of setting)
Time
(sec)
2 3 4 5 6 8 20 30 40 50 60 80
100
Long Time Inverse
Normal Inverse
Very Inverse
Extremely Inverse
Fig 2. IEC Overcurrent Curves
0.1
1
10
100
1000
110
Current (multiples of setting)
Time
(sec)
2 3 4 5 6 8 20 30 40 50 60 80
100
Moderately Inverse
Extremely Inverse
Very Inverse
Fig 3. ANSI Overcurrent Curves
Description of Functionality