ENGINEERING INFORMATION AND INSTRUCTIONS
MICROMASTER
MICROMASTER Vector
MIDIMASTER Vector
SIEMENS DA 64 – 2002/2003
Version D 3/22
Class 2: Filtered industrial environments
For this level, manufacturers/companies assembling electrical equipment can themselves certify that their equipment is in
conformance with the EMC Directive for industrial environments referred to the EMC characteristics of the motor drive system. In
this case, the limit values, specified in the Standards EN 50081-2 and EN 50082-2 apply (VDE 0839 Part 81-2 and VDE 0839 Part
82-2).
EMC Phenomena Standard Level
Emission:
Radiated emission EN 55011 (VDE 0875 Part 11) Level A1
Cable-borne emission EN 55011 (VDE 0875 Part 11) Level A1
Noise immunity:
Line supply voltage distortion EN 61000-2-4 (VDE 0839 Part 2-4)
Voltage fluctuations, dips, unbalance, frequency deviations IEC 1000-2-1
Magnetic fields EN 61000-4-8 (VDE 0847 Part 4-8) 50 Hz, 30 A/m
Electrostatic discharge (ESD) EN 61000-4-2 (VDE 0847 Part 4-2) 8 kV discharge into air
Burst interference EN 61000-4-4 (VDE 0847 Part 4-4) 2 kV power cable, 2 kV control
Radio frequency electromagnetic field, amplitude-modulated ENV 50 140 (VDE 0847 Part 3) 80 - 1000 MHz, 10 V/m, 80 % AM, line
supply and signal cables
Radio frequency electromagnetic field,
pulse modulated
ENV 50 204 (VDE V 0847 Part 204) 900 MHz, 10 V/m 50 % utilization, 200 Hz
repetition rate
Class 3: Filtered – for residential, commercial and light industry
For this level, manufacturers/companies assembling electrical equipment can themselves certify that their equipment is in
conformance with the EMC Directive for residential, commercial and light industrial operations referred to the EMC characteristics of
the motor drive system. In this case, the limit values, specified in Standards EN 50081-1 and EN 50082-1 (VDE 0839 Part 81-1 and
VDE 0839 Part 82-1) apply. Since the 1
st
of January 2001, all electrical equipment, which fall within the validity area of the EMC
Directive, must fulfill the requirements laid-down in EN 61000-3-2 "Limit values for harmonic currents (equipment input current <=
16 A per phase)". For drives with 250 W to 550 W and 230 V AC 1-phase line supplies, which are not used in industrial
applications, then authorization is required from the power supply company (public utility) to connect the equipment to the public
supply. More detailed information is provided in EN 61000- 3-12, Section 5.3 and 6.4 or in Section 1.3.3 Limit values for harmonic
currents in non-industrial applications EN 61000-3-2
EMC Phenomena Standard Level
Emission:
Radiated emission EN 55022 (VDE 0878 Part 22) Level B1
Cable-borne emission EN 55022 (VDE 0878 Part 22) Level B1
Noise immunity:
Electrostatic discharge (ESD) EN 61000-4-2 (VDE 0847 Part 4-2) 8 kV discharge into air
Burst interference EN 61000-4-4 (VDE 0847 Part 4-4) 1 kV power cable, 0.5 kV control
Note
MICROMASTER, MICROMASTER Vector and MIDIMASTER Vector have been exclusively designed for professional
applications. This means that they do not fall under the Standard EN 61000-3-2 (VDE 0838 Part 2, limit values for harmonic
currents for drive inverter input current = 16 A per conductor).
Compliance table (MM & MMV):
Type EMC Class
MM12 - MM300, MMV12 - MMV300 Class 2
MM12/2 - MM400/2, MMV12/2 - MMV400/2 Class 1
MM12/2 - MM400/2, MMV12/2 - MMV400/2 with external filter (refer to Table) only 1 phase input Class 2*
MM37/3 - MM750/3, MMV37/3 - MMV750/3 Class 1
MM37/3 - MM750/3, MMV37/3 - MMV750/3 with external filter (refer to the selection table) Class 2*
Compliance table (MDV):
Type EMC Class
MDV550/2 - MDV4500/2 Class 1
MDV750/3 - MDV7500/3 with external Class A filter (refer to Table) Class 2*
MDV750/3 - MDV3700/3 with external Class B filter (refer to Table) Class 3
MDV750/4 - MDV3700/4 Class 1
* When installed in a metal housing, the emitted radio frequency field is reduced and generally limit values, Class 3 are maintained.