Strona 1 - RuggedMC™ RMC30

RuggedMC™ RMC30Installation GuideRuggedCom Inc.300 Applewood Crescent,Concord, OntarioCanada L4K 5C7 Web: http://www.ruggedcom.com/Tel: +1 905 856 52

Strona 2 - 2 RuggedMC™

2.3 Power Supply Wiring and GroundingDrawing 5 - RuggedMCTM Power Supply InputsThe RuggedMCTM power supply inputs are identical and are connected as f

Strona 3 - Important:

2.4 Serial Ports – Signal DescriptionThe RMC30 is equipped with a seven-terminal phoenix style connector. This connector can accommodate one RS232 co

Strona 4 - Table of Contents

2.4.1 RS232 Data PortThe RMC30 is equipped with a single EIA/TIA RS232 compliant port, consisting of three terminals: Transmit, Receive, and Common.

Strona 5 - 1 Product Overview

2.4.2 RS422 and RS485 Data PortsThe RMC30 is equipped with a single RS485 / RS422 data port. In half duplex mode (See section 2.5 for RMC30 configura

Strona 6 - 6 RuggedMC™

Drawing 8 - Conceptual RS485 wiring diagramRuggedCom® 14 RuggedMC™ RMC30 Installation Guide Rev 105

Strona 7 - Side and Bottom View

2.5 RMC30 Quick Start RecommendationsThe following is an excerpt from the RMC30 User's Guide. It is included to aid those users experienced with

Strona 8 - 2 Installation

3 Technical Specifications3.1 Power Supply SpecificationsPower Supply Type Minimum InputMaximum InputInternalFuseRatingMaximum Power Consumption24 VD

Strona 9 - 2.2 Panel Mounting

3.2 Mechanical SpecificationsDrawing 9 - RMC30 Mechanical DimensionsParameter Value CommentsDimensions4.30 x 2.40 x 3.30 inches(110) x (61) x (84)

Strona 10 - 10 RuggedMC™

3.3 Operating EnvironmentParameter Range CommentsAmbient Operating Temperature-40 to 85°CAmbient Temperature as measured from a 30cm radius surroundin

Strona 11 - RS422: Rx +/- & Tx+/

4 Type Test Specifications4.1 IEC 61850-3 Type TestsIEC 61850-3 EMI TYPE TESTSTest Description Test Levels Severity LevelsIEC 61000-4-2 ESD Enclosure

Strona 12 - Connector

CopyrightCOPYRIGHT © 2010 RuggedCom Inc. ALL RIGHTS RESERVEDDissemination or reproduction of this document, or evaluation and communication of its co

Strona 13 - 13 RuggedMC™

D.C. Power ports 30V Continuous, 300V for 1s4IEC 61000-4-17 Ripple on D.C. Power SupplyD.C. Power ports 10% 3IEC 60255-5 Dielectric Strength Signal po

Strona 14 - 14 RuggedMC™

4.3 IEC Environmental Type TestsENVIRONMENTAL TYPE TESTSTest Description Test Levels Severity LevelsIEC 60068-2-1 Cold Temperature Test Ad -40°C, 16

Strona 15 - Console mode

5 Agency ApprovalsAgency Standards CommentsCSA, CE CSA C22.2 No. 60950, UL 60950, EN 60950EN 61000-6-2ApprovedFCC FCC Part 15, Class AApprovedCISPR EN

Strona 16 - 3 Technical Specifications

Federal Communications Commission Radio Frequency Interference StatementThis equipment has been tested and found to comply with the limits for a Class

Strona 17 - 3.2 Mechanical Specifications

Table of Contents1 Product Overview...

Strona 18 - 3.3 Operating Environment

1 Product OverviewINTRODUCTIONThe RuggedServer™ RMC30 is an industrially hardened, 2-port serial device server that has been specifically designed to

Strona 19 - 4 Type Test Specifications

1.1 RMC30 Front Panel DescriptionThe RMC30 LED definitions are as follows:LED Activity DescriptionPower Solid (Green) Power OnAlarm Solid (Red) Alarm

Strona 20 - 4.2 IEEE 1613 Type Tests

1.2 RMC30 Side and Bottom ViewDrawing 2- RMC30 Side and Bottom ViewRuggedCom® 7 RuggedMC™ RMC30 Installation Guide Rev 105

Strona 21 - ENVIRONMENTAL TYPE TESTS

2 Installation2.1 DIN Rail MountingDrawing 3 - RMC30 DIN Rail MountingRuggedCom® 8 RuggedMC™ RMC30 Installation Guide Rev 105

Strona 22 - 6 Warranty

2.2 Panel MountingWith the use of an optional panel-mount adapter, the RuggedMCTM series of media converters can be panel mounted. Drawing 4 shows an

Komentarze do niniejszej Instrukcji

Brak uwag