Siemens RUGGEDCOM RSG2200 Dokumentacja Strona 14

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 46
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 13
Chapter 2
Installing Device
RUGGEDCOM RSG2200
Installation Guide
8 Connecting Power
Figure 4: Panel Mounting
1. Screw 2. Panel/DIN Rail Adaptor
2. Install the supplied screws to secure the adapters to the panel.
Section 2.2
Connecting Power
The RSG2200 supports single or dual redundant AC and/or DC power supplies. The use of two power modules is
recommended to provide redundancy and load balancing.
The RSG2200 can be equipped with either a screw-type or pluggable terminal block, which provides power
to both power supplies. The screw-type terminal block is installed using Philips screws and compression
plates, allowing either bare wire connections or crimped terminal lugs. Use #6 size ring lugs for secure, reliable
connections under severe shock or vibration.
NOTE
For maximum redundancy in a dual power supply configuration, use two independent power
sources.
For 100-240 VAC rated equipment, an appropriately rated AC circuit breaker must be installed.
For 125/250 VDC rated equipment, an appropriately rated DC circuit breaker must be installed.
A circuit breaker is not required for 12, 24 or 48 VDC rated power supplies.
It is recommended to provide a separate circuit breaker for each power supply module.
Przeglądanie stron 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 45 46

Komentarze do niniejszej Instrukcji

Brak uwag