Outputs
85
Building Technologies
Fire Safety & Security Products
Output B Options
P35E 1-8E 1-8E
Option Display text Description
1
AC Fail
Mains Fail to Output: this option is used to assign a Mains Fail alarm to an output.
2
Fuse Fail
Fuse Failure to Output: this option is used to assign a Fuse Failure alarm to an
output. The on-board fuses are thermally activated. If excessive current is drawn from
a fuse it will disconnect the power until the problem is resolved. There are two thermal
fuses protecting the various 12 V DC outputs.
3
Battery Low
Battery Low to Output: this option is used to assign a Battery Low alarm to an output.
4
Line Fail
Telephone Line Failure to Output: this option is used to assign a Telephone Line
Failure alarm to an output.
5
Zone Supervisory
Fail
Supervisory Radio failure to Output: this option is used to assign a Radio Detector
Supervisory Fail alarm to an output.
6
Sensor Watch
Fail
Sensor-Watch Alarm to Output: this option is used to assign a Sensor-Watch alarm to
an output. A Sensor-Watch alarm occurs when a detector has not operated within a
set period of time.
7
System Tamper
System Tamper to Output: this option is used to assign a panel tamper alarm to an
output.
8
Receiver Fail
Receiver Fail to Output: if the receiver fail timer expires (see chapter 13.7: Receiver
fail delay-timer; Radio Reset Time; P25E 7E) this option will assign the alarm to an
output.
Output C Options
P36E 1-8E 1-5E
Option Display text Description
1
Walk Test Pulse
Walk-test Pulse to Output: when the panel is in Walk-test Mode, this option assigns a
pulse to the output every time a zone is triggered. The pulse is linked to the Output
Pulse time (P39E).
2
Blink when Idle
Pulse Output every 5 seconds when Disarmed : this option will cause the output to
pulse every 5 seconds when the panel is disarmed. The pulse time is linked to the
Output Pulse time (P39E).
3
Dial Arming
Acknowledge
Pulses Output
Pulse Output on Kiss-off Following Arming: this option will cause the output to pulse
for 2 seconds when the panel is armed and the message has been kissed off by the
monitoring company. The pulse time is linked to the Output Pulse time (P39E) which
is defaulted to 2 seconds.
4
Dial Zone Alarm
Acknowledge
Pulses Output
Pulse Output on Kiss-off After a zone alarm: this option will cause the output to pulse
for 2 seconds when the panel is armed and the message has been kissed off by the
monitoring company. The pulse time is linked to the Output Pulse time (P39E).
5
Disable during
dial delay
Valid as of version 9.07:
Output Disabled when P25E 3E timer is running: this option will cause the Output to
be disabled when the dialer reporting delay is active. It is designed to keep external
audible alarms silent when the dial delay is active (allowing internal alarms to warn
that the alarm will be reported to monitoring if not unset) but if the alarm hasn’t been
reset before the timer expires the external alarm will sound.
According EN 50131-3 if an alarm occurred during Exit Delay the dialer should
reported only after 30sec.
And the Siren shouldn't activate until the Exit delay is expired.