Plan deployment
3.4 Producing the installation cut-out
TP 270, OP 270, MP 270B (WinCC flexible)
3-6 Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
MP 270B 10" Keys, OP 270 10"
Notice
The following air flow requirements must be maintained following installation:
-50 mm above the HMI device
-15 mm below the HMI device
- 15 mm at the sides of the HMI device
When using plug-in boards, ensure sufficient space is provided to insert or remove them.
For installation in a front panel, the MP 270B 10" Keys or TP 270 10" requires an installation
cut-out (WxH) of 436
+1
mm x 295
+1
mm. The thickness of the front panel must not exceed 6
mm.
OP 270 6"
Notice
The following air flow requirements must be maintained following installation:
- 100 mm above the HMI device
- 50 mm below the HMI device
- 15 mm at the sides of the HMI device
When using plug-in boards, ensure sufficient space is provided to insert or remove them.
For installation in a front panel, the OP 270 6" requires an installation cut-out (WxH) of 282
+1
mm x 178
+1
mm. The thickness of the front panel must not exceed 6 mm.