Adding and Configuring Devices ION Setup User Guide
Page 52 © 2010 Schneider Electric. All rights reserved.
1. Right-click the workstation icon and select Insert Item. The New Network
Item dialog box appears.
2. Select Site and click OK. The New Site dialog box appears. Select the General
tab.
3. Type a name identifying the site in the Name box.
4. Select Ethernet from the Comm Link options then select the Gateway
checkbox.
5. Type the IP address of the gateway device and select the port number from the
dropdown list in Gateway Info.
6. Edit the values on the Timings and Polling, if needed. These tabs contain other
site communications parameters which, in most cases, do not need to be
modified from the default settings. See “Editing Site Properties” on page 55 for
information regarding the settings on these tabs.
7. Click OK. The site is added to the network viewer.
You can now add devices to your site; see “Adding a New Meter” on page 53.
If supported, you can connect to and read data from your gateway device by
adding it as a stand-alone Ethernet device in ION Setup; see “Adding a New
Meter” on page 53.
Configuring the ION7550 / ION7650 meter as a Modbus
gateway
Before configuring an ION7550 / ION7650 as a Modbus gateway, make sure the
ION7550 / ION7650 meter is connected to the Ethernet, your serial meters are
wired to the gateway meter, and basic setup has been performed on each device,
including the gateway meter.
See “Using Ethernet Gateways or Modbus Gateways” on page 17 for general
information on Ethernet gateway communications and network setup.
NOTE
For Modbus TCP communications, the Ethernet IP port is hard-coded to port 502 on ION7550/ION7650
meters. You do not need to set this in ION Setup.
IP Port Description
502 Modbus TCP
7800 EtherGate simultaneously though available COM ports of an ION meter
7801 EtherGate through COM1 of an ION meter
7802 EtherGate through COM2 or COM4 of an ION meter
7803 EtherGate through COM3 of an ION meter