Loadable Drivers
7-4
System Software for M7-300 and M7-400 Installation and Operation
C79000-G7076-C850-02
Loading the 3964 Driver
The following examples illustrate how to load the 3964 driver.
In the rmos.ini file
Load 3964 driver in the rmos.ini file without generating a unit:
DEVICE = \M7RMOS32\3964.DRV
Load 3964 driver and unit for COM1 with default:
DEVICE = \M7RMOS32\3964.DRV COM1 IRQ:4 BASE:0x3F8
MODE:19200–N–8–1 PROT:1–1
The driver is loaded and a unit named COM1 is generated with the following
driver-specific parameters: 19 200 bit/s, no parity bit, 8 data bits, 1 stop bit,
3964R protocol, master.
In CLI:
Generate a driver unit for 3964 on COM2:
DEVICE 3964 3964_COM2 IRQ:3 BASE:0x2F8 MODE:19200
–N–8–1 PROT:1–1
Loading the SER8250 Driver
The following examples illustrate how to load the SER8250 driver.
In the rmos.ini file
Load SER8250 driver without generating a unit:
DEVICE = \M7RMOS32\SER8250.DRV
Load SER8250 driver and unit for COM1 with default:
DEVICE = \M7RMOS32\SER8250.DRV COM1 IRQ:4
BASE:0x3F8 MODE:19200–N–8–1
The driver is loaded and a unit named COM_1 is generated with the following
driver-specific parameters: 19 200 bit/s, no parity bit, 8 data bits, 1 stop bit.
In CLI:
Generate a driver unit for SER8250 on COM2:
DEVICE SER8250 COM2 IRQ:3 BASE:0x2F8 MODE:9600*N*8*1