Manual No. MCC-3298SAMMS-LVSiemens Advanced Motor Master System forLow Voltage MotorsUser's Manual12345678910111213141516™
82 Installing the SAMMS-LV DeviceFigure 2.1 Full voltage non-reversing connection diagram
92 Installing the SAMMS-LV Device2.4.2 Grounding the DeviceAs stated in Guideline 5, ground each motor controller at asingle ground point. The groundi
102 Installing the SAMMS-LV Deviceenables the SAMMS-LV to communicate with a remote super-visory device. Examples of the remote supervisory deviceincl
113 Operating the SAMMS-LV Device3 Operating the SAMMS-LV DeviceThis section explains how to operate the SAMMS-LV device.Operation of the device requi
123 Operating the SAMMS-LV Device3.4 Output DevicesYou can use the following SAMMS-LV output devices:AC OutputsThe SAMMS-LVX device provides up to thr
133 Operating the SAMMS-LV Device3.6 Ladder Diagrams3.6.1 Library of Standard Ladder DiagramsThe SAMMS-LV library of more than 70 ladder diagrams cove
143 Operating the SAMMS-LV Device12345678 9 10 11 12131415 16SAMMS-LVXLEDLED on LED FlashingCurrentUnbalanceImpendingTripOverloadTripIncompleteSequenc
153 Operating the SAMMS-LV DeviceInput AssignmentsStarterTypeProgramBlockControl Type PB1 PB2 PB3 PB4 PB5 PB6Preloaded inSAMMS-LVE,can bedownloaded in
163 Operating the SAMMS-LV DeviceInput AssignmentsStarterTypeProgramBlockControl Type PB1 PB2 PB3 PB4 PB5 PB6Available withSAMMS-LVXonlyRVA(Auto TX)Si
173 Operating the SAMMS-LV Device3.7 Incomplete SequenceSometimes the motor contactors do not respond in a timelymanner to start, stop, transition, sp
The use of unauthorized parts in the repair of the equipment or tampering byunqualified personnel will result in dangerous conditions which will cause
183 Operating the SAMMS-LV DeviceFigure 3.5 ODP motor thermal signature
193 Operating the SAMMS-LV Device100001000100101.1110SECONDSIratioIFLC100001000100101.1110SECONDSIratioIFLCFigure 3.6 Time-current characteristic curv
203 Operating the SAMMS-LV DeviceFigure 3.9 Time-current characteristic curve for warm motors with SF=1.15Figure 3.8 Time-current characteristic curve
213 Operating the SAMMS-LV Device.1 1IIFLCratio610Motor starting current600% rated full load currentJam and loss of loadprotection persistencedelay (5
223 Operating the SAMMS-LV Deviceof 10 guarantees that a current of 600% of IFLC will cause a tripin 10 seconds or less. In the SAMMS-LV, the protecti
233 Operating the SAMMS-LV Device3.19 Stator ProtectionBy selecting the overload class slightly greater than or equal tothe motors starting time, the
243 Operating the SAMMS-LV Devicethe motor trips and the Ground Fault LED illuminates until reset.If you selected warning (OFF), the Ground Fault LED
253 Operating the SAMMS-LV DeviceSAMMS-LVFunction Number Function SAMMS-LVX SAMMS-LVEF0 Ambient temperature• •F1 Control circuit number• •F2 Size for
263 Operating the SAMMS-LV Device3.27.1 The (F)unction KeyWhen you press the (F)unction key, the function mode isselected and the HHC displays the num
273 Operating the SAMMS-LV DeviceFunctionNumberFunction Description Range Step Size Default ValueF0 Select ambient temperature. 0 - 70º C 5º C 40º CF
11 Introduction ...21.1 About this Manual ... 31.2 About the SAMMS-
283 Operating the SAMMS-LV DeviceFunctionNumberFunction Description Range Step Size Default ValueF12 Select ground fault protection orwarning. ON mea
293 Operating the SAMMS-LV DeviceFunctionNumberFunction Description Range Step Size Default ValueF18 Display the elapsed motor running timein tens of
303 Operating the SAMMS-LV DeviceFigure 3.13 Entering and changing passwordsFPress and hold F keyUP DOWNDisplaymodeProgrammodeENTER ENTERUP DOWNTo sel
313 Operating the SAMMS-LV DeviceTo change the password:1. Enter the password as described above.2. With the password entered and the display showing
323 Operating the SAMMS-LV DeviceF4 - Full-Load Current for Overload Relay #11. Press the LIST key to view the active full-load current settingfor ove
333 Operating the SAMMS-LV Device6. Press the (F)unction key to step through to another function.F6 - Service Factor1. Press the LIST key to view the
343 Operating the SAMMS-LV Deviceb.When phase unbalance protection is disabled (OFF), thePhase Unbalance LED remains off, unbalanced condi-tions have
353 Operating the SAMMS-LV DeviceF12A - Ground Fault Pickup Current1. Press the LIST key to view the active ground fault pickupcurrent in use. The ran
363 Operating the SAMMS-LV DeviceF17 - Current Unbalance1. Press the LIST key to view the percentage current unbal-ance. When unbalance protection is
373 Operating the SAMMS-LV Device3. To change the protection setting, press the UP or DOWNkey to display ON or OFF, then press ENTER to select thesett
21 Introduction1 IntroductionThe SAMMS-LV electronic motor control and protectiondevice is designed and manufactured in accordance with thelatest app
383 Operating the SAMMS-LV DeviceF27 - Address1. Press the LIST key to view the active setting. Allowableaddresses are 1-224. The factory default is 2
394 Troubleshooting4 Troubleshooting the SAMMS-LVDeviceThis section discusses how to troubleshoot the SAMMS-LVdevice. The troubleshooting guide belo
404 TroubleshootingTroubleshooting GuideError Condition Main Cause RemedyIncompleteSequenceIndicates the SAMMS-LV unit does notdetect current one seco
414 TroubleshootingTroubleshooting GuideError Condition Main Cause RemedyGround Fault Indicates the ground fault currentexceeded the threshold. If gro
42Appendix A Technical SpecificationsAppendix A - Technical Specifications of the SAMMS-LV DeviceMotor Control SpecificationsInputs SAMMS-LVX:Six push
43Appendix A Technical SpecificationsFLCFLCFLCFLCFLCFLCFLCFLCFLCFLCFLCFLCFLCFLCFLCFLCFLCFLCOverload SpecificationsOverload classes Overload classes 2
44Appendix A Technical SpecificationsSoftware Configured Control DevicesTimers 4Timing range Timers 1 and 2: 0 - 200 seconds selectableTimer 3: 1 se
45Appendix A Technical SpecificationsDimensionsSAMMS-LV 6.25 inches W; 6.00 inches H; 2.125 inches DHandheld Communicator 3.15 inches W; 5.7 inches H;
46Appendix A Technical SpecificationsFigure A-1Figure A-1Figure A-1Figure A-1Figure A-1 Catalog Number and Configuration Breakdown for SAMMS-LVSAMMS-L
47Appendix A Technical SpecificationsSAMMS-LVXLEDLED onLED FlashingCurrentUnbalanceImpendingTripOverloadTripIncompleteSequenceExternalTrip AlarmCPUFau
31 Introduction1.1 About this ManualThis manual introduces you to the Siemens Advanced MotorMaster System (SAMMS-LV) motor protection and control rela
48Appendix A Technical SpecificationsFigure A-4 SAMMS 5A Auxiliary Current Transformer and SAMMS sensors (sizes 1A-6)SIZE A B C D E F G H I J5A ACT 4.
Siemens Energy &Automation, Inc.Switchgear and Motor ControlDivisionP.O. Box 29503Raleigh, NC 27626-0503Bulletin MCC-3298 (New) 3M 0994FP Printed
41 Introduction12345678910111213141516Figure 1.1 SAMMS-LV, front view1.2.1 The SAMMS-LV Device ModelsThe SAMMS-LV device is available in two models: S
51 IntroductionFigure 1.2 Hand-Held Communicator (HHC)1.2.3 Overload ProtectionThe motor model offers the selection of overload classes 2through 23.Th
61 IntroductionSAMMS-LV Model SAMMS-LVE SAMMS-LVXApplicationAcross-the-line, non reversingX XAcross-the-line, reversingXTwo-speed, one winding, consta
72 Installing the SAMMS-LV Device2 Installing the SAMMS-LV DeviceThis section provides instructions for installing the SAMMS-LVdevice. You should adap