Further AS-i System Components
3-5
SIMATIC NET AS-Interface Introduction and Basic Information
C79000-G8976-C089/03
3.3 Installing an AS-i Module
The installation of an AS-i module on the AS-i cable is particularly simple using the
connection technique described. This is made clear by the following illustration:
Figure 3-2
1. The coupling module is screwed or clipped
onto a 35 mm standard rail. The coupling
module includes four stoppers. These are
used to close unused cable openings.
Figure 3-3
2. The AS-i cable is inserted. It locks into a
guide above the contact blades and is
secured mechanically. No electrical contact
is established. Two stoppers are inserted in
the unused cable opening.
Figure 3-4
3. By screwing down the application module,
the AS-i cable is pressed onto the contact
blades. They penetrate the conductors at
two points and guarantee a reliable
connection. After correct installation, the
module has the type of protection IP67.