Siemens SIMATIC Distributed I/O System DP/ASi Link Instrukcja Obsługi Strona 51

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 64
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 50
The Master Mode Commands, Sequence, Programming
4-11
SIMATIC NET AS-Interface Introduction and Basic Information
C79000-G8976-C089/03
4.2.3 Operating Extended AS-i Slaves with Standard AS-i Masters
Note
Please note the following information about operating extended AS-i slaves with
standard AS-i masters!
S If A slaves are connected to standard masters, make sure that the most
significant slave bit (bit 4) of each A slave is set to 0. The most significant
parameter bit (bit 4) must also be set to 1 (default value).
Without these settings, the A slave cannot be operated with a standard master.
S B slaves must not be connected to standard AS-Interface masters.
-
Przeglądanie stron 50
1 2 ... 46 47 48 49 50 51 52 53 54 55 56 ... 63 64

Komentarze do niniejszej Instrukcji

Brak uwag