
Wiring the S7-400
4-10
Automation System S7-400 Hardware and Installation
A5E00850741-01
4.7 Assembling an S7-400 with Isolated Modules
Definition
In a configuration with isolated modules, the reference potentials of the control
circuit ( M
internal
) and the load circuit (M
external
) are isolated (see also Figure 4-4).
Application
Isolated modules are used for:
• All AC load circuits
• DC load circuits with a separate reference potential
Examples of load circuits with a separate reference potential:
-- DC load circuits whose sensors have different reference potentials (for
example, when grounded sensors are used far from the programmable
controller and equipotential bonding is not possible).
-- DC load circuits whose positive terminal (L+) is grounded (battery circuits).
Isolated Modules and Grounding Concept
You can use isolated modules, regardless of whether or not the reference potential
of the programmable controller is grounded.
Komentarze do niniejszej Instrukcji