43
© EPCOS AG 2015
Please read Important notes on page 4 and Cautions and warnings on page 5.
Bitte beachten Sie die Seite 4 Wichtige Hinweise sowie die Warn- und Sicherheitshinweise auf Seite 5.
Medium-duty / High-voltage types
10 kA / 10 A
l
ø 8 × 8 mm
A71-…
7.9±0.3
ø1
+0.2
0.4
ø8
_
Type
Ordering code
A71-H08X
B88069X2140S102
A71-H10X
B88069X3820S102
A71-H12X
B88069X2090S102
A71-H14X
B88069X2180S102
A71-H16X
B88069X2610S102
Nom. DC spark-over voltage V
sdcN
800 1000 1200 1400 1600 V
Tolerance of V
sdcN
±15 ±15 ±20 ±20 ±20 %
Impulse spark-over voltage
@ 100 V/µs 99% of
measured values
< 1100 < 1300 < 1900 < 2100 < 2300 V
@ 100 V/µs typical values < 1000 < 1200 < 1800 < 2000 < 2200 V
@ 1 kV/µs 99% of
measured values
< 1200 < 1400 < 2000 < 2200 < 2400 V
@ 1 kV/µs typical values < 1100 < 1300 < 1900 < 2100 < 2300 V
Service life
10 operations 50 Hz, 1 s 10 10 10 10 10 A
1 operation 50 Hz, 9 cycles 65 65 65 65 65 A
10 operations 8/20 µs 10 10 10 10 10 kA
1 operation 8/20 µs 10 10 10 10 10 kA
Insulation resistance > 10 > 10 > 10 > 10 > 10 GΩ
Capacitance @ 1 MHz < 1 < 1 < 1 < 1 < 1 pF
About packing see page 71.
2-Electrode Arresters
2-Elektroden-Ableiter
Komentarze do niniejszej Instrukcji