DP Master Module
6-2
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
6.1 Mounting the DP master module
When you expand your interface module IM 151-7 CPU with a DP master module,
you can use the IM 151-7 CPU as a DP master.
Procedure
Step Description
1 The IM 151-7 CPU is installed on the mounting rail.
2 Hang the DP master module onto the mounting rail to the right of the
IM 151-7 CPU.
3 Swivel the DP master module down until it engages.
4 Slide the DP master module to the left until it engages audibly in the IM 151-7
CPU.
5 If required, mount terminal modules for power/electronics modules and slide the
corresponding modules into the TM.
SF
BF
ON
FRCE
RUN
STOP
IM 151-7 CPU DP master module
BF
4
2
DP master
interface
3
Figure 6-2 Mounting the DP master module