Installation
4.1 Installation requirements
41
4 Installation
4.1 Installation requirements
To ensure the installation of the inverter under the right environmental conditions, the following guidelines
must be adhered to.
The inverters are designed with IP20 protection. This means:
They are protected against the ingress of solid foreign bodies with a size of 12.5 mm.
They are not protected against the ingress of water.
They are intended for installation in indoor areas.
The inverter must be stored and operated within the acceptable temperature ranges.
Proper ventilation and air currents must be provided.
Proper grounding procedures must be used on each inverter.