Siemens SITRANS P Instrukcje Operacyjne

Przeglądaj online lub pobierz Instrukcje Operacyjne dla Narzędzia pomiarowe i układowe Siemens SITRANS P. Siemens SITRANS P Operating instructions Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 234
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów

Podsumowanie treści

Strona 1 - Pressure transmitter

Answers for industry.SITRANSPressure transmitterSITRANS P, DS III Series with HARTOperating Instructions· 09/2012

Strona 2

A.2 Literature and standards...215 A.3 Liter

Strona 4

Operating functions through HART77.1 Operating functions through HART communicationConditionYou can operate the transmitter through HART communication

Strona 5

7.2 Process tag dataYou can store your process tag data in user definable fields. The following table contains information about the structure of thes

Strona 6

The following device variables are activated only when the allocated measuring mode is activated and parameterized simultaneously:●"Level",

Strona 7

four variables, all other device variables are marked as inactive and have the CONSTANT status. These four variables are mapped with dynamic variables

Strona 8

In the device, the characteristic curve vertices are only provided once in the EEPROM. Therefore, if the measuring mode is changed, you will usually n

Strona 9

with appropriate parameters. Only then will you be given a meaningful measured value for the three device variables. 3UHVVXUH6HQVRUWHPSHUDWXUH(OHFWURQ

Strona 10 - Table of contents

,QSXWVFDOLQJ3UHVVXUH&DOFXODWLRQH[DPSOH0$ EDU0( EDUS EDU&DOFXODWLRQH[DPSOH0$ 0( 2XWSXW /HYHOFKDU

Strona 11

7.3.7 Measuring mode "Flow rate"Description When you activate the "Flow rate" measuring mode, only two other device variables are

Strona 12 - 1.5 Checking the consignment

NoteWhen using the "Flow rate" block, other square root extracting characteristic curves must be deactivated if required. '9>@

Strona 13 - 1.7 Notes on warranty

Introduction11.1 Purpose of this documentationThese instructions contain all information required to commission and use the device. It is your respons

Strona 14

7.3.8 Measuring mode "User"DescriptionThe "User" measuring mode is the simplest of the measuring modes that you can select with th

Strona 15 - Safety instructions

'96HQVRU3UHVVXUH6HQVRUWHPSHUDWXUH(OHFWURQLFVWHPSHUDWXUH/LQHDUL]DWLRQ2II0HDVXULQJPRGHVZLWFK0HDVXULQJPRGHV3UHVVXUH6HQVRUFDOLEUDW

Strona 16 - 2.2 Use in hazardous areas

characteristic curve vertices. These curve shapes can be stored in the device using SIMATIC PDM or the HART communicator.In the calculation example, t

Strona 17

The basic measured values, namely pressure and temperatures, have the BAD status in the following cases:●The analog-to-digital converter does not func

Strona 18

)ORZUDWH&KDUDFWHULVWLFFXUYH6WDWXVLGHQWLILHU'96HQVRU3UHVVXUH6HQVRUWHPSHUDWXUH(OHFWURQLFVWHPSHUDWXUH/LQHDUL]DWLRQ2II0HDVXULQJP

Strona 19

DV Measuring modeBAD MANUAL UNCERTAIN CONSTANT HIGH LIMIT LOW LIMIT3 Pressure (untrimmed)Analog-to-digital converter in over/underrange, DV1 sensor br

Strona 20 - 3.2 Application range

7.3.10 Analog outputIntroductionThe "Analog output" block converts the value provided by the dynamic primary variable (PV) into a current va

Strona 21 - 3.3 Structure

Description of measuring mode "Level"3ULPDU\9DULDEOHVURIIVUOLVUOLOLQHDUS EDU39OHYHOP,QSXWVFDOLQJ0$0(&DOFXODWLRQH[

Strona 22

ExampleIn the Level measuring mode, the start of scale value is assumed as 0 m and the full scale value as 10 m in the example illustrated in the foll

Strona 23 - 3.4 Nameplate layout

7.5 Blind setting of zero point and limit point● The start of scale value and the full scale value can be set without creating a reference pressure. ●

Strona 24 - SITRANS P

Edition Remark09/2012 The following chapters have been changed:●"General safety notices" chapter● "Mounting" chapter● "Functi

Strona 25 - 3.6 Functional principle

7.7 Electrical dampingDescriptionYou can set the time constant of electrical damping to a point within a range from 0 to 100 s. It always applies to t

Strona 26 - Overview

See alsoError display (Page 69)Limit modules (Page 131)7.11 Setting the current limitsDescriptionThe level of the upper and lower fault current and th

Strona 27

7.12 Key lock and write protectionIntroductionYou can use this function to lock the keys or activate write protection to safeguard the saved parameter

Strona 28

7.13 Measured value displayIntroductionYou can use this function to set one of three options for the device display:● Display in mA● Display in % (of

Strona 29

● If the pressure unit is < 5 characters, an A or a G is added at the end, respectively.●If the pressure unit is ≥ 5 characters, the letters GAUGE

Strona 30

7.15 Bar graphDescriptionYou can use this to switch on the "Bar graph" function in the device display as an alternative to the unit display.

Strona 31

7.16.2 Trimming the sensorTrim the sensor at the lower trim pointThe pressure at which the lower sensor trim is to be performed is applied at the tran

Strona 32

Example of an applicationThe current is to be measured as a voltage drop from 1 to 5 V at a resistance of 250 Ohm +/- 5%. To trim the tolerance of the

Strona 33 - 3.8 SIMATIC PDM

DescriptionYou can use the menu-guided interface of SIMATIC PDM or HART Communicator to select the range of parameters to be reset:1.Current trim2. Se

Strona 34

● Sensor seal diaphragm material●Transmitter model● Housing material● Tube length● Process connection● Electrical connection● Process connection screw

Strona 35 - Installing/mounting

1.6 Transportation and storageTo guarantee sufficient protection during transport and storage, observe the following:● Keep the original packaging for

Strona 36 - 4.1 Basic safety instructions

Variable application pointThe output current for the "srlin" and "sroff" functions can be displayed linearly or set to zero below

Strona 37 - ① Flameproof joint

required, refer to the attached table for operation of the HART Communicator or the help functions in the SIMATIC PDM software.7.21.2Operating hours c

Strona 38

When the warning/alarm limit has been reached, the following applies:1. "Alarm/Acknowledge the request" resets the request / alarm message,

Strona 39

7.21.5 Limit modulesIntroductionThe diagnostic functions of this device give you an option to monitor the measured values in programmable limits. If t

Strona 40 - 4.1.2 Proper mounting

Example 1: the response time starts at t1. At t1, current reaches the configured saturation limit of 20.5 mA for the first time. At t2, the response t

Strona 41 - 4.2 Disassembly

7.22 Simulation7.22.1 Overview of simulationDescriptionWith the "Simulation" diagnostic function, you can receive and process simulated meas

Strona 42 - Installation configuration

7.22.2 Simulation as fixed valueDescriptionTaking the physical unit into account you can set a fixed simulation value for all three possible simulatio

Strona 43 - 4.3.3 Fastening

Hysteresis Operating point for chatter suppression in the case of small pressure changes.Response time The time which must pass after the limit is vio

Strona 44

Reset event counter upper limit Here you can reset the upper limit counter to zero. A new event is not possible until the counter has been reset.Reset

Strona 45 - Requirements

Functional safety88.1 General safety instructions8.1.1Safety-instrumented systemThis chapter describes the functional safety in general and not specif

Strona 47 - Assembly on an open container

Function principle of multi-channel operation Automation system0HDVXUHGYDOXH6KXWGRZQVLJQDOTransmitterFinal controlling elementsFigure 8-2 Safet

Strona 48

The "average probability of dangerous failures of the entire safety-instrumented system" (PFDAVG) is normally split between the three sub-sy

Strona 49

8.2 Device-specific safety information for single-channel operation (SIL 2)8.2.1 Safety functionSafety function for pressure transmitters The safety

Strona 50

Checking the safety function NoteYou should check the safety function while the device is mounted, if possible. If this is not possible, you can a

Strona 51

● Explosion protection for corresponding versions●Electromagnetic compatibility in compliance with EN 61326 8.2.4 Behavior in case of faultsRepairsDef

Strona 52

● The SITRANS P pressure transmitter is only used in applications with a low demand for the safety function (low demand mode).●Communication with the

Strona 53

NoteUse of remote sealsIf remote seals are used, the application-specific measurement error is the product of the transmitter and remote seal measur

Strona 54

The PLC program must monitor the measured values of both DS III devices. As soon as the measured values differ by e.g. 2% or more, the system must be

Strona 55

● Check the measuring accuracy, which must be within the range of the application-specific measuring error for the safety function. – Set the measure

Strona 56

Checking safety You should regularly check the safety function of the entire safety circuit in accordance with IEC 61508/61511. The testing interval

Strona 57 - 4.7 Rotating the display

Safety instructions22.1 Precondition for use This device left the factory in good working condition. In order to maintain this status and to ensure sa

Strona 58

WARNINGAdd-on parts unsuitable for process mediumDanger of injury or damage to device.If the process medium is not suitable for the parts which com

Strona 59 - Connecting

Commissioning99.1 Basic safety instructions DANGERToxic gases and liquidsDanger of poisoning when the device is vented.If toxic process media are me

Strona 60 - 5.1 Basic safety instructions

NoteHot surfacesHot process medium and high ambient temperatures lead to hot surfaces which can cause burns.●Take corresponding protective measures

Strona 61

9.3 gauge pressure, absolute pressure from the differential pressure series and absolute pressure from the gauge pressure series9.3.1 Commissioning fo

Strona 62 - Connecting the device

ProcedureTo commission the transmitter for gases, proceed as follows:1.Open the shut-off valve for the test connection ④.2. Via the test connection of

Strona 63 - Closing the device

RequirementAll valves are closed.ProcedureTo commission the transmitter for steam or liquid, proceed as follows:1.Open the shut-off valve for the test

Strona 64 - 5.3 Connecting the Han plug

9.4.2 Commissioning in gaseous environmentsUsual arrangement Special arrangement① Pressure transmitter ⑥ Shut-off valves② Stab

Strona 65

3. Open the differential pressure valve (③ or ④).4. Check and if required correct the zero point when the start of scale value is 0 mbar (4 mA).5. Clo

Strona 66 - ② Positioning catch

Procedure WARNINGThe transmitter should not be depressurized if toxic substances are being used. To commission the transmitter with liquids, proceed

Strona 67 - Operation

9.4.4 Commissioning with vapor① Pressure transmitter ⑦ Drain valves② Stabilizing valve ⑧ Condensate pots③, ④Differential pressure val

Strona 68 - Basic safety instructions

Electromagnetic Compatibility EMC 2004/108/ECDirective of the European Parliament and of the Council on the approximation of the laws of the Member St

Strona 69 - 6.4 Display

3. Wait until the steam in the differential pressure lines ⑤ and in the equalizing vessels ⑧ has condensed.4.Open the differential pressure valve ③ an

Strona 70 - 6.4.2 Units display

Service and maintenance1010.1 Basic safety instructions WARNINGImpermissible repair of explosion protected devicesDanger of explosion in areas subje

Strona 71 - 6.4.3 Error display

WARNINGMaintenance during continued operation in a hazardous areaThere is a danger of explosion when carrying out repairs and maintenance on the de

Strona 72 - 6.4.5 Status display

WARNINGImproper connection after maintenanceDanger of explosion in areas subject to explosion hazard.●Connect the device correctly after maintenanc

Strona 73 - 6.4.6 Overflow range

NOTICEElectrostatic-sensitive devices The device contains electrostatic-sensitive devices (ESD). ESD can be destroyed by voltages far too low t

Strona 74 - 6.5 Local operation

10.2.2 Checking the gasketsInspect the seals at regular intervals NoteIncorrect seal changesIncorrect measured values will be displayed. Changing the

Strona 75 - Operating functions

In case of defect, you can replace the electronic unit by following the warning notes and the provided instruction manual. See alsoError display (Page

Strona 76 - 6.5.2 Operation using buttons

NOTICEPenetration of moisture into the deviceDevice damage.● Make sure when carrying out cleaning and maintenance work that no moisture penetrates

Strona 77

10.4 Return procedureEnclose the bill of lading, return document and decontamination certificate in a clear plastic pouch and attach it firmly to the

Strona 78

NoteSpecial disposal requiredThe device includes components that require special disposal.●Dispose of the device properly and environmentally throu

Strona 79

● They are authorized, trained or instructed in operating and maintaining devices and systems according to the safety regulations for electrical circu

Strona 81 - Setting start of scale value

Technical data1111.1 Overview of technical dataIntroductionThe following overview of technical data provides you with a quick and easy access to relev

Strona 82

11.2 Input pointGauge pressure input HART PROFIBUS PA or Foundation FieldbusMeasured variable Gauge pressureSpan (continuously adjustable) or measuri

Strona 83 - Adjusting full scale value

gauge pressure input, with flush mounted diaphragm HART PROFIBUS PA or Foundation FieldbusMeasured variable Gauge pressureMeasuring span (continuousl

Strona 84

Absolute pressure input, with flush-mounted diaphragm HART PROFIBUS PA or Foundation FieldbusLower measuring limit 0 bar a (0 psi a)Upper measuring

Strona 85 - Example of blind adjusting

Absolute pressure input (from the gauge pressure series) HART PROFIBUS PA or Foundation FieldbusMeasured variable Absolute pressureMeasuring span (co

Strona 86

Absolute pressure input (from the differential pressure series) HART PROFIBUS PA or Foundation FieldbusMeasured variable Absolute pressureMeasuring s

Strona 87

Differential pressure and flow rate input HART PROFIBUS PA or Foundation FieldbusMeasured variable Differential pressure and flow rateMeasuring span

Strona 88

Differential pressure and flow rate input HART PROFIBUS PA or Foundation Fieldbus for process temperature of -20°C < ϑ ≤ 60°C (-4°F < ϑ ≤ +140

Strona 89 - 6.5.6 Trimming the zero point

11.3 OutputOutput HART PROFIBUS PA or Foundation FieldbusOutput signal 4 … 20 mA Digital PROFIBUS-PA or Foundation Fieldbus signal● Lower limit (cont

Strona 90 - 6.5.7 Current transmitter

WARNINGUse of incorrect device parts in potentially explosive environmentsDevices and their associated device parts are either approved for differe

Strona 91

Measuring accuracy (as per EN 60770-1) gauge pressure HART PROFIBUS PA or Foundation FieldbusMeasurement deviation with cut-off point setting, includ

Strona 92

Gauge pressure measuring accuracy, with flush mounted diaphragm HART PROFIBUS PA or Foundation Fieldbus● r ≤ 10 ≤ (0.0029 • r + 0.071) % –● 10 < r

Strona 93 - Releasing key lock

Measuring accuracy (as per EN 60770-1) DS III with PMC connection HART PROFIBUS PA or Foundation FieldbusLong-term drift at ±30° C (±54° F) In 5 year

Strona 94 - Fixed application point

Absolute pressure measuring accuracy (from gauge and differential pressure series) HART PROFIBUS PA or Foundation FieldbusInfluence of mounting posit

Strona 95

Differential pressure and flow rate measuring accuracy HART PROFIBUS PA or Foundation FieldbusEffect of the ambient temperature (double values for me

Strona 96 - 6.5.12 Measured value display

Level measuring accuracy HART PROFIBUS PA or Foundation Fieldbus Measuring cell 250 mbar (3.63 psi)≤ (0.5 • r + 0.2) % ≤ 0,7 %Measuring cell 600 mba

Strona 97 - 6.5.13 Unit

Rated conditions for gauge pressure and absolute pressure (from the gauge pressure series)● Degree of protection in accordance with EN 60529IP65, IP68

Strona 98

Conditions of use for gauge pressure and absolute pressure with flush-mounted diaphragm● Measuring cell with Neobee (FDA-compliant)-10 … +150°C (14 …

Strona 99

Rated conditions for absolute pressure (from the differential pressure series), differential pressure and flow rate● Degree of protection in accordanc

Strona 100

11.6 ConstructionConstruction for gauge pressure and absolute pressure (from the gauge pressure series)Weight Approx. 1.5 kg (3.3 lb) for aluminum en

Strona 101 - See also

Description33.1 System configurationOverviewThe pressure transmitter can be used in a number of system configurations:●as a stand-alone version, suppl

Strona 102 - 7.2 Process tag data

Construction for gauge pressure, with flush mounted diaphragm Electronics housing ● Non-copper aluminum die casting GD-AlSi 12 or stainless steel pre

Strona 103 - 7.3.3 Variable mapper

DS III construction with PMC connection● Standard ● Flush mounted●11/2''● PMC Standard design● Minibolt ● Flush mounted●1''● PMC M

Strona 104

Design for absolute pressure (from the differential pressure series), differential pressure and flow rateElectrical connection Screw terminalsCable in

Strona 105 - Description

Construction for level● Mounting flange fill fluid Silicon oil or a different designProcess connection ● Plus side Flange as per EN and ASME● Minus s

Strona 106 - ME Full scale value

Auxiliary power UH HART PROFIBUS PA or Foundation Fieldbus● Max. basic current – 12.5 mA● Starting current ≤ basic current – Yes● Max. current in eve

Strona 107

Certificates and approvals HART PROFIBUS PA or Foundation Fieldbus Marking II 1 D IP65 T 120 °C, II 1/2 D IP65 T 120 °CPermissible ambient tempera

Strona 108

11.9 HART communicationHART communicationLoad for a ● HART communicator connection 230 … 1100 Ω● HART modem 230 … 500 ΩCable 2-wire, shielded: ≤ 3.0

Strona 109

Dimension drawings1212.1 SITRANS P, DS III series for gauge pressure and absolute pressure from the gauge pressure series(1.14)15(0.6)74 (2.9)143 (5

Strona 110

① Key cover② Blanking plug③ Cover catch (only for "flameproof enclosure" type of protection)④ Electrical connection:●Threaded joint Pg 13.5

Strona 111

12.2 SITRANS P, DS III series for differential pressure, flow rate and absolute pressure from the differential pressure series15(0.6)80 (3.15)143 (5.6

Strona 113 - Change in status

3.2 Application rangeOverviewDepending on the version, a transmitter measures corrosive, non-corrosive and hazardous gases, vapors and liquids.You can

Strona 114

① Key cover② Blanking plug③ Cover catch (only for "flameproof enclosure" type of protection)④ Mounting bracket (optional)⑤ Lateral ventilati

Strona 115 - LIMIT are swapped around

80 (3.15)15(0.6)143 (5.6)53 (2.1)ca. 96 (3.78)17(0.67)29(1.14)84 (3.31)128 (5.04)ca. 217 (8.54)ca. 87 (3.43)ca. 85 (3.35)min 90 (3.54)60 (2.36)65 (2.5

Strona 116 - 7.3.10 Analog output

12.3 SITRANS P, DS III series for level29(1.14)177 (6.97)84 (3.31)54 (2.1)108 (4.25)ca. 96 (3.78)17(0.67)bLn x d2fd5d4KD15(0.6)143 (5.6)74 (2.9)53 (2.

Strona 117

① Key cover② Blanking plug③ Cover catch (only for "flameproof enclosure" type of protection)④ Process connection: Minus side 1/4-18 NPT (EN

Strona 118

12.4 SITRANS P, DS III series (flush mounted) 15(0.6)74(2.9)53(2.1)143(5.6)15(0.6)min. 90 (3.54)H1 = ca. 130 (5.12)80 (3.15)H2 = ca. 55 (2.17)(0.94)2

Strona 119 - Procedure

12.4.1 Note 3A and EHDG NoteApprovalsThe references to the approvals for "EHEDG" and "3A" refer to the respective process connect

Strona 120 - 7.10 Fault current

Flanges as per ASMEASME B 16.5 DN CLASS ⊘D H2 '+1'' 150 110 mm (4.3'') Approx. 52 mm (2'')1'' 300 125 m

Strona 121

DIN 11864-2 Form A - sterile collar flange DN PN ⊘D H2 '+50 16 94 mm (3.7'') Approx. 52 mm (2'')65 16 113 mm (4.4'&apo

Strona 122 - Lock options

Other connectionsVarivent® connector DN PN ⊘D H2 '+40-125 40 84 mm (3.3'') Approx. 52 mm (2'')Approvals EHEDGConnection in

Strona 123 - 7.13 Measured value display

BioConnectTM flange connector DN PN ⊘D H2 '+50 16 110 mm (4.3'') Approx. 52 mm (2'')65 16 140 mm (5.5'')80 16 150

Strona 124

Level This version with mounting flange measures the level of non-corrosive, corrosive and hazardous liquids in open and closed containers. The smal

Strona 125 - 7.16 Sensor calibration

Other connectionsBioControlTM connector DN PN ⊘D H2 +'50 16 90 mm (3.5'') Approx. 52 mm (2'')65 16 120 mm (4.7'')

Strona 126 - Current sensor trim

12.4.5 Special connectionsTank connection TG52/50 and TG52/150 DN PN ⊘D H2 +'TG52/5043.5 mm 10 63 mm (2.5'') Approx. 63 mm (2.5&apo

Strona 127 - Factory calibration

IDF connectorsIDF sockets with union nut DN PN ⊘D H2 +'2" 25 77 mm (3.0'') Approx. 52 mm (2.1'')2½" 25 91 mm (3.6

Strona 128 - Static configuration data

Spare parts/accessories1313.1 Order dataIn order to ensure that the ordering data you are using is not outdated, the latest ordering data is always av

Strona 129

Selection and order data Order no.For transmitter for absolute pressure (7MF423.-...-..A., -..B. and -..D.) ● Made of steel 7MF4997-1AC● Made of st

Strona 130 - 7.21 Diagnostic functions

Selection and order data Order no.● Made of stainless steel 7MF4997-1CG● Made of Hastelloy 7MF4997-1CHVent valves, complete (1 set = 2 pieces) ● Made

Strona 132 - /RZHUGUDJLQGLFDWRUSRLQW

AppendixAA.1 CertificateThe certificates can be found on the enclosed CD and on the Internet under:Certificates (http://www.siemens.com/processinstrum

Strona 133 - 7.21.5 Limit modules

No. Title Publisher Order no./4/ Catalog ST 80 SIMATIC HMI operation and observation productsSiemens AG E86060-K4680-A101-B4/5/ Catalog IK PI Industri

Strona 134

A.4 Overview of HART operating structureThe following overview applies to the HART communicator operating structure. 2 Online 1 (PV meas) *) 2 (

Strona 135 - 7.22 Simulation

① Key cover ⑧ Cable inlet, optionally with cable gland② Cover (front), optionally with inspection window ⑨ Cover (rear) for electrica

Strona 136 - 7.23 Limit monitor

3 Volume scaling 1 Volume unit 2 Vol LRV 3 Vol URV 2 Density unit 3 Density 3 Mass unit 6 (measurement) config 1 Input scaling 1 Pres abs/r

Strona 137

4 LCD Settings 1 LCD Scaling, if On: 2 LCD Unit 5 Bargraph 3 LCD LRV 4 LCD URV 6 Access Control 1 Lokal keys control mode 2 Write protect

Strona 138

A.5 Technical supportTechnical Support You can contact Technical Support for all IA and DT products:● Via the Internet using the Support Request:

Strona 139 - Functional safety

List of abbreviationsB List of abbreviationsTable B-1UnitsAbbreviation In full Meaningbar a bar absolute Pressure unit for absolute pressurebar g bar

Strona 140

Abbreviation Full term in English MeaningMooN "M out of N" voting Classification and description of the safety-instrumented system in terms

Strona 141 - Operational reliability

GlossaryATEXATEX is an abbreviation of the French term "Atmosphère explosible" (potentially explosive atmosphere). ATEX stands for both EC d

Strona 142 - 8.2.2 Settings

Fault→ Failure/FaultFault toleranceFault tolerance N means that a device can execute the intended task even when N faults exist. The device fails to e

Strona 143 - 8.2.3 Requirements

Non-volatile memory→ EEPROMRiskThe combination of probability of a damage occurring and its magnitude.Safety functionDefined function executed by a sa

Strona 144 - 8.2.6 Safety characteristics

The achievable SIL is determined by the following safety characteristics:●Average probability of dangerous failure of a safety function in case of dem

Strona 145 - 8.3.1 Safety function

Index PVPrimary variable, 102 QVQuarternary variable, 102 SVSecondary variable , 102 TVTertiary variable, 10233A, 203AAcknowledgement, 129Additional

Strona 146 - 8.3.2 Requirements

3.4 Nameplate layoutNameplate with general informationThe nameplate bearing the Order No. and other important information, such as design details and

Strona 147 - 8.3.3 Settings

FFactory calibration, 125Failure current, 118Fast recording of measured values, 118Fast Response Mode, 118Filling liquid, 25, 27, 28Final controlling

Strona 148 - 8.3.5 Maintenance/Checking

Pressure simulation, 134Pressure unit, 122Primary variable, 71, 94Process connection, 20PVPrimary variable, 94QQualified personnel, 14RRamp function,

Strona 151 - Commissioning

$($(www.siemens.com/processautomationSubject to change without prior noticeA5E00047092-08© Siemens AG 2012Siemens AGIndustry Automat

Strona 152

Nameplate with approval informationOn the opposite side is the nameplate with approval information. This nameplate shows e.g. the hardware and firmwar

Strona 153

3.6 Functional principle3.6.1 Overview of mode of operationThis chapter describes how the transmitter works.First the electronics are described, and t

Strona 154

Function●The input pressure is converted into an electrical signal by the sensor ①.● This signal is amplified by the measuring amplifier ② and digitiz

Strona 155 - Requirement

● Flange connection in accordance with EN 61518●Flush-mounted process connections3.6.3.1 Measuring cell for gauge pressureSH① Reference pressur

Strona 156

3.6.3.2 Measuring cell for differential pressure and flow rate① Inlet pressure P+⑥ Overload diaphragm② Pressure cap ⑦ Filling liquid③ O-ri

Strona 157

3.6.3.3 Measuring cell for level  ① Pressure cap ⑥ Seal diaphragm on the measuring cell② O-ring ⑦ Filling liquid of the measuring cell③ Me

Strona 158

SITRANSPressure transmitterSITRANS P, DS III series with HARTOperating Instructions7MF4.33.. 09/2012A5E00047092-08Introduction 1 Safety instructions 2

Strona 159

3.6.3.4 Measuring cell for absolute pressure from the differential pressure seriesSH① Pressure cap ⑥ Overload diaphragm② Seal diaphragm on th

Strona 160

● The change in the resistance causes a bridge output voltage proportional to the absolute pressure.3.6.3.5Measuring cell for absolute pressure from t

Strona 161 - Service and maintenance

The inlet pressure (pe) is transferred to the gauge pressure sensor ⑥ via the seal diaphragm ④ and the filling liquid ⑤, displacing its measuring diap

Strona 162

3.7 Remote sealProduct description ● A remote seal measuring system comprises the following elements:– Remote seal– Transmission line, e.g. capillary

Strona 164

Installing/mounting44.1 Basic safety instructions WARNINGWetted parts unsuitable for the process mediaDanger of injury or damage to device. Hot, tox

Strona 165 - 10.2.2 Checking the gaskets

NoteMaterial compatibilitySiemens can provide you with support concerning selection of sensor components wetted by process media. However, you are

Strona 166 - 10.3 Cleaning

WARNINGIncorrect conduit systemDanger of explosion in hazardous areas as result of open cable inlet or incorrect conduit system.●In the case of a c

Strona 167 - Cleaning the enclosure

WARNINGLoss of explosion protectionDanger of explosion in hazardous areas if the device is open or not properly closed.●Close the device as describ

Strona 168 - 10.5 Disposal

4.1.1 Installation location requirements WARNINGInsufficient air supplyThe device may overheat if there is an insufficient supply of air.●Install th

Strona 169

Legal informationWarning notice systemThis manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent

Strona 170

4.1.2 Proper mounting4.1.2.1Incorrect mounting NOTICEIncorrect mountingThe device can be damaged, destroyed, or its functionality impaired through im

Strona 171 - Technical data

4.2 Disassembly WARNINGIncorrect disassemblyThe following dangers may result through incorrect disassembly: - Injury through electric shock- Danger

Strona 172 - 11.2 Input point

● Easily accessible●As close as possible to the measuring point● Vibration-free● Within the permitted ambient temperature valuesInstallation configura

Strona 173

4.3.3 FasteningFastening without the mounting bracketYou can fasten the transmitter directly on the process connection.Fastening with the mounting bra

Strona 174

Figure 4-2 An example of fastening the transmitter on the mounting bracket in the case of differential pressure and horizontal differential pressure l

Strona 175

Figure 4-3 An example of fastening on the mounting bracket in the case of differential pressure and vertical differential pressure lines4.4"Level

Strona 176

NoteProtect the transmitter from:●Direct heat● Rapid temperature changes● Severe soiling● Mechanical damage● Direct sunlight NoteSelect the height o

Strona 177

4.4.3 Connection of the negative pressure lineAssembly on an open containerA line is not required when taking measurements in an open container since

Strona 178

Assembly on a closed containerWhen taking measurements in a closed container without or with little condensate formation, the negative pressure line i

Strona 179 - 11.4 Measuring accuracy

'-K2K8)XOOVFDOHYDOXH6WDUWRIVFDOHYDOXH0D[LPXPOHYHO6WDWLFSUHVVXUH&RQVWDQWFRPSDULVRQOHYHO/LTXLGILOOHGORZSUHVVXUHOLQH7UDQVPLWWHUUHIHU

Strona 180

Table of contents1 Introduction...

Strona 181

● Never loosen the sealed filling screws on the remote seal and the measuring instrument.●Do not cause damage to the remote separating membrane; scrat

Strona 182

4.5.2 Installation of the remote seal with the capillary lineNotes ●Do not rest the measurement assembly on the capillary line.● Do not bend capillary

Strona 183

+++X+RPressure transmitter below the measuring point Start of scale value: pMA = ρFL * g * HU - ρoil * g * H1Full-scale value: pME = ρFL * g * HO -

Strona 184

SDEV+ Pressure transmitter for absolute pressure always below the measuring point: H1 ≥ 200 mm (7.9 inch)Key pMAStart of scale valuepMEFull-scale

Strona 185 - 11.5 Operating conditions

Installation type for differential pressure and flow rate measurementsInstallation type D ++9+Start of scale value: pMA = pstart - ρoil * g * HVFu

Strona 186

Key pMAStart of scale valuepMEFull-scale valueρFLDensity of the process medium in the containerρoilDensity of the filling oil in the capillary line o

Strona 187

Installation type J ++Between the measuring points, no vacuumH2 ≤ 7 m (23 ft); with halocarbon oil as the filling liquid, only H2 ≤ 4 m(13.1 ft)St

Strona 188

① Turning range② Retaining screw③ Orientation markFigure 4-4 Example: turning range of transmitters for pressure and absolute pressure from the g

Strona 189 - 11.6 Construction

3. Screw the covers back on as far as they will go.4.Secure the covers with the cover catch. Installing/mounting4.7 Rotating the displaySITRANS P, DS

Strona 190

Connecting55.1 Basic safety instructions5.1.1Unsuitable cables and/or cable glands WARNINGUnsuitable cables and/or cable glandsDanger of explosion in

Strona 191

4.1.2.1 Incorrect mounting...38

Strona 192

WARNINGUnsafe extra-low voltageDanger of explosion in hazardous areas due to voltage flashover.●Connect the device to an extra-low voltage with saf

Strona 193

WARNINGConnecting device in energized stateDanger of explosion in hazardous areas.●Connect devices in hazardous areas only in a de-energized state.

Strona 194

NoteElectromagnetic compatibility (EMC)You can use this device in industrial environments, households and small businesses.For metal housings there

Strona 195

3. Connect the wires to the terminals "+" and "-". ④Observe the correct polarity. If necessary, ground the device using the "

Strona 196 - 11.9 HART communication

3. Close the key cover ①.4.Tighten the screws in the key cover.5. Check the tightness of the blanking plugs ⑤ and cable gland ② in accordance with the

Strona 197 - Dimension drawings

Procedure1.Slide the sleeve and the screwed joint on the cable.2. Strip approx. 8 mm of the cable ends.3. Crimp the contact parts on the cable ends.4.

Strona 198

6. Screw the cable ends and the shield in the pin insert.7.Fix the parts of the cable jack as described by the connector manufacturer.Figu

Strona 199

Operation66.1 Overview of operationIntroductionThe following description contains an overview of the operating functions that you can execute using th

Strona 200

Function Using buttons Using HARTCharacteristic curve (lin., rad.) (Not relevant for absolute and gauge pressure)Yes YesCustomized characteristic curv

Strona 201

6.4 Display6.4.1 Display elementsStructure① Measured value ⑤ Violation of lower limit② Unit/bar graph ⑥ Symbol for measured value③ Root displ

Strona 202

6.5.5.4 Blind adjusting of the start of scale value...86 6.5.5.5 B

Strona 203

6.4.2 Units displayDescriptionThe unit display comprises five 14-segment fields for representing the unit as a percentage value, physical unit or curr

Strona 204 - ① Key cover ⑤ Connection side

6.4.3 Error displayDescriptionIf hardware faults, software errors or diagnostic alarms occur in the transmitter, the message "Error" appears

Strona 205 - 12.4.1 Note 3A and EHDG

6.4.4 Mode displayDescriptionThe selected active mode is shown in the mode display.DisplayFigure 6-4 Example for mode displayIn the example, a damping

Strona 206 - Connections as per DIN

Function Mode Display Display Position correction 7 if the max span is exceeded by more than 5% of the upper current limitif the value falls below th

Strona 207

See alsoFault current (Page 118)Setting the current limits (Page 119)6.5 Local operation6.5.1 Local control elementsIntroductionThe transmitter can be

Strona 208 - connectors

Operating functions NoteZero point calibrationFor absolute pressure transmitters, the start of scale value is at vacuum.A zero point calibration with

Strona 209

Function Mode Key function Display, explanations[M] [↑] [↓] [↑] and [↓]Key lock or function lock10 Switch between the five functions– 0 NoneLA all loc

Strona 210 - 12.4.4 PMC Style

ProcedureIn the default setting, the device is in the measured value display.To adjust the operating functions, proceed as follows:1.Loosen both the s

Strona 211 - 12.4.5 Special connections

Depending on the series and measuring range, a maximum downscaling of 1:100 can be achieved (measuring span ratio = r, turn down). The correla

Strona 212 - IDF connectors

C 14 bar process pressure is created. Use the [M] button to set the transmitter to mode 3. To set the full scale value, press the [↑] and [↓] buttons

Strona 213 - Spare parts/accessories

7.19 Static configuration data...126 7.20 Fl

Strona 214 - 13.1 Order data

Example of adjusting with reference pressureA Initial situationSUHI0$DFWXDOYDOXH0$VHWSRLQWYDOXH0$DFWXDOYDOXH0$VHWSRLQWYDOXH0(VHWSRLQW

Strona 215

6.5.3.2 Setting/adjusting the start of scale value NOTICEInadvertent adjustment of parameters on devices without display or without visible displayK

Strona 216

Setting the start-of-scale value without a displayYou have a device with a cover that does not have an inspection window and you wish to set the start

Strona 217 - Appendix

3. Set the full scale value to 20 mA.4.Save with the [M] button.Adjusting full scale valueIf you do not set the output current but constantly adjust i

Strona 218 - A.3 Literature and catalogs

6.5.4 Setting/adjusting electrical dampingDifference between setting and adjustingYou can set or adjust the time constant of electrical damping using

Strona 219

6.5.5 Blind start of scale value/full scale value6.5.5.1Difference between setting/adjusting and blind setting/adjustingDifferencesIn contrast to sett

Strona 220

Explanations for the blind adjusting exampleA The measuring range is from 0 to 16 bar. You are changing the start of scale value from 0 to 2 bar and t

Strona 221

ConditionYou are familiar with the correct operation of the transmitter and the associated safety notes.You have not created any reference pressure an

Strona 222 - A.5 Technical support

6.5.5.4 Blind adjusting of the start of scale valueIntroductionIn the case of blind adjustment, adjust the pressure value of the start of scale value

Strona 223 - List of abbreviations

ConditionYou are familiar with the correct operation of the transmitter and the associated safety notes.You have not created any reference pressure an

Strona 224 - B.1 Functional safety

9.4.4 Commissioning with vapor...15710 Service

Strona 225 - Glossary

1. Create the reference pressure.2.Set mode 7.3. Set the reference pressure on the display.4. Save using the [M] key. 6.5.7 Current transmitterIntrodu

Strona 226 - Frequency shift keying

6.5.8 Output current in case of faultIntroductionWhen a fault occurs, the upper fault current is displayed in the basic setting. In mode 9, you can ch

Strona 227

6.5.9 buttons and function lockIntroductionIn mode 10, you can disable the functions that can be executed using buttons. Application example for a loc

Strona 228

ConditionYou are familiar with the correct operation of the transmitter and the associated safety notes. NoteIn the measured value display function,

Strona 229

● linear "lin": proportional to differential pressure ●square root extracting "sroff": proportional to flow rate, deactivated up

Strona 230

     VTXDUHURRWH[WUDFWLQJ/LQHDUSUHVVXUH3UHVVXUH>@2XWSXW>@Characteristic curves and application p

Strona 231

6.5.12 Measured value display NoteTo use the operating functions with the buttons, first set the device variable (DV) parameters with a host system s

Strona 232

See alsoMeasured value display (Page 121)6.5.13 UnitIntroductionIn mode 14, select the physical unit in which the measured value display of the device

Strona 233

UnitsTable 6-7Units available for pressurePressure units Display Pressure units Displaymbar mbar Psi PSibar bar Pa Pamm water column (20°C / 68°F)

Strona 234 - $(

Table 6-11 Units available for temperatureTemperature unit Display Temperature unit Display° Celsius ° / C Kelvin K° Fahrenheit ° / F Rankine RTab

Komentarze do niniejszej Instrukcji

Brak uwag