Page 158 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
If your PMD is not listed, select the appropriate Universal Flow Calculation.
Associated parameters Max Head (P603), Max Flow (P604), and Min Head (P605) may be
scroll accessed. If Operation is not set for OCM (P001 = 6), this value is preset to 0. If
Operation is set for OCM, it is preset to 1.
P601 Flow Exponent
The Exponent for the flow calculation formula.
Use this parameter if the Primary Measuring Device (P600) is set to 1 (exponential). It
creates an exponential curve with end points set by Max Head (P603) and Zero Head
(P604) and with the curve based on the specified exponent.
Alters
• P601 Flow Exponent
• P602 Primary Measuring Device Dimensions
• P608 Flowrate Units
Altered By •P001 Operation
Related
• P603 Maximum Head
• P604 Maximum Flow
• P605 Zero Head
• P610 Head Breakpoints
• P611 Breakpoint
Primary Index Global
Values
Range: -999 to 9999
Preset: 1.55
Altered By • P600 Primary Measuring Device
Related
• P603 Maximum Head
• P604 Maximum Flow
• P605 Zero Head
Max. Flow
(P604)
Zero Flow
Zero Head
Max. Head
(P603)
If P601 = 1, the flow characteristic is a straight line
Use the exponent specified by the
PMD manufacturer, or the sample
value given below.
A Word on Exponents
The exponential equation is
Q = KH
P601
Where:
Q = flow
K = internal constant
H = head