UMSITRPDS3-1 On-Line Operation
November 2010
6-31
The default setting for all warnings and alarms is OFF. To set and enable:
1. In the Online menu, press 3 Device Setup.
2. In the Device Setup menu, press 2 Diagnostics/Service.
3. In the Diagnostics/Service menu, press 1 Diagnosis
4. In the Diagnosis menu, press 3 Warnings/Alarms. Refer to the Online Configuration Map in
Appendix A and to the HART Communicator’s help screens.
6.4.19.1 Operating Hours Counter
Two operating hours counters with non-volatile memories are provided for the electronics and the sensor.
These counters are not re-settable. If power is removed and later reapplied, the counters begin counting
from the previous time. To read the operating hours counters:
1. In the Online menu, press 3 Device Setup
2. In the Device Setup menu, press 2 Diagnosis/Service
3. In the Diagnosis/Service menu, press1 Diagnosis
4. In the Diagnosis menu, press 2 Operating Hours
5. In the Operating Hours menu, press 1 Operating Hours Electronics or 2 Operating Hours Sensor. The
total operating hours will be displayed.
6.4.19.2 Calibration Timer and Service Timer
A two-stage time can be set to ensure regular calibration of the electronics and servicing of the
transmitter. A calibration or service warning appears after the first time expires. On expiration of a second
time, set as a time difference, a diagnostic alarm is signaled and a fault current is output.
A warning or alarm must be acknowledged before work can be performed on the transmitter. Timers can
then be reset and switched off temporarily.
For operating/acknowledging warnings and alarms in the HART Communicator, the following applies:
As long as the warning/alarm limit has not been reached:
“Reset” resets the timer and begins again with the counter at 0. Monitoring is still active.
“Acknowledge” has no effect, the timer continues running and the monitoring is still active.
“Reset and deactivate” stops the timer, resets it, and deactivates the monitoring.
When the warning/alarm limit has been reached:
“Acknowledge” resets the warning/alarm message but the timer continues to run. In this state, no new
alarm or warning is possible since the time limits will still have to be exceeded.
“Reset” resets the warning/alarm message the timer. At the same time, the alarm or warning is
acknowledged. The timer runs again immediately from zero and will respond again when the
warning/alarm limit is exceeded. The next calibration interval is therefore immediately activated.
“Reset and ActivateW/A” resets the warning/alarm message and resets and deactivated the timer.