Appendix C: Device Data Format
110 Siemens Energy & Automation, Inc.
Restr. Curr. Of L3 at Trip
(average DC)
36 High word
Restr. Earth Flt.: Value D at Trip 37 ms since fault (-1 = no occurrence)
Restr. Earth Flt.: Value D at Trip 38 Low word
Restr. Earth Flt.: Value D at Trip 39 High word
Restr. Earth Flt.: Value S at Trip 40 ms since fault (-1 = no occurrence)
Restr. Earth Flt.: Value S at Trip 41 Low word
Restr. Earth Flt.: Value S at Trip 42 High word
Transformer Tank Prot.: Value
at Trip
43 ms since fault (-1 = no occurrence)
Transformer Tank Prot.: Value
at Trip
44 Low word
Transformer Tank Prot.: Value
at Trip
45 High word
Fault in the power system 46 ms since fault (-1 = no fault)
General Trip of Device 47 ms since fault (-1 = no occurrence)
Trip by thermal overload
protection 1
48 ms since fault (-1 = no occurrence)
Trip by thermal overload
protection 2
49 ms since fault (-1 = no occurrence)
Back-up Overcurrent: General
Trip
50 ms since fault (-1 = no occurrence)
External Trip 1: General Trip 51 ms since fault (-1 = no occurrence)
External Trip 2: General Trip 52 ms since fault (-1 = no occurrence)
Diff. Prot.: Blocked by
harmonics L1
53 ms since fault (-1 = no occurrence)
Diff. Prot.: Blocked by
harmonics L2
54 ms since fault (-1 = no occurrence)
Diff. Prot.: Blocked by
harmonics L3
55 ms since fault (-1 = no occurrence)
Differential Protection: Gen-
eral Trip
56 ms since fault (-1 = no occurrence)
Differential Protection: L1 57 ms since fault (-1 = no occurrence)
Differential Protection: L2 58 ms since fault (-1 = no occurrence)
Differential Protection: L3 59 ms since fault (-1 = no occurrence)
Differential Protection: Trip by
Idiff>
60 ms since fault (-1 = no occurrence)
Differential Protection: Trip by
Idiff>>
61 ms since fault (-1 = no occurrence)
Restr. Earth Flt.: General Trip 62 ms since fault (-1 = no occurrence)
Transformer Tank Prot.: Gen-
eral Trip
63 ms since fault (-1 = no occurrence)
Reserved 64–67 For Future Expansion
1. Status information for each parameter is transmitted in two bits. The status bit indicates status (true = 1, false = 0) for the parameter
and the valid bit indicates that the device has successfully updated the value in the status bit (true = 1, false = 0).
Real-Time Device Data Stored in PLC (7UT513) (Continued)
Function Register Location in
PLC Block
Range or Contents