Siemens SIMATIC NET PROFIBUS Instrukcje Operacyjne Strona 367

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 366
Infrared Link Modul (ILM)6ZB5530–3AC30–0BA1
25
Copyright by Siemens
6.4 Operation with Signaling Contact
The signaling contact is used to monitor the PROFIBUS ILM via a digital input on a PLC or as part of a current
loop. If problems occur the contact opens, in other words a connected current loop is then interrupted. By
setting four switches, the user decides which events trigger the signaling contact. If more than one problem is
configured to trigger the signaling contact, the problem cannot be localized using the signaling contact alone. In
this case, the LED displays can also provide information and step-by-step disabling of the switches that
activate the signaling contact can narrow down the problem.
Note
Remember that if you want to activate the signaling contact when the acknowledgment pulse is absent, the
monitor link with acknowledgment pulse configuration must be activated.
Przeglądanie stron 366
1 2 ... 362 363 364 365 366 367 368 369 370 371 372 ... 489 490

Komentarze do niniejszej Instrukcji

Brak uwag