Configuring Networks
3-20
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Power Budget for OLM G11-1300, G12-1300 for One Point-to-Point
Link at Wavelength
λ = 1310 nm
Attenuation on the cable
Fiber type
Attenuation
a
FOC
Cable length
L
62.5/125 µm 1.0 dB/km 9 km L* a
FOC
= 9.0 dB
+
Attenuation for connectors
a
Conn
Number
+
1 dB 0 Number *
a
Conn
0 dB
Attenuation caused by splices +
a
Spl
Number
0.2 dB 5 Number * a
Spl
1.0 dB
Attenuation of the transmission path a
Path
= 10.0 dB
Data of the OLM/G11-1300, G12-1300 power that
can be coupled into 62.5/125 µm fibers
P
out,
min
17 dBm
Receiver sensitivity
Prec
,
min
29 dBm
Maximum permitted attenuation a
max
= P
out,
min
P
rec,
min
= 12 dB
Link power margin a
max
a
Path
= 2 dB
The transmission path can be implemented as planned.