Overview of PROFIBUS DP
DP Base Programming Interface for CP 5613/CP 5614
C79000-G8976-C108-01
27
2.8 Reliability of DP
Reliability Concept
The DP programming interface provides various mechanisms to limit the effects of
the failure of a communication connection or the DP master.
x
A watchdog function can be configured on the DP slave so that if a slave is not
accessed for a longer period of time it can change automatically to a safe state.
x
The AUTOCLEAR function can be activated to ensure that if DP slaves are not
accessible, the master automatically changes to the CLEAR mode.
x
A sign-of-life monitoring function can be activated on the DP master that
recognizes inactivity of a DP user program so that the DP slaves controlled by
the master can be changed to a safe state (for the software version in which this
function is available, refer to the version table in Section of the installation
instructions).
The AUTOCLEAR function
The AUTOCLEAR option can be set during configuration. If an error occurs on one
or more DP slaves during the productive phase, the DP master then changes
automatically
to the AUTOCLEAR mode (the DP system is closed down). The
AUTOCLEAR mode is the same as the CLEAR mode. The DP master then sends
data with the value 0 or empty frames in the output direction to the DP slaves. The
DP master can no longer exit this mode automatically; in other words, the change
to the OPERATE mode must be triggered explicitly by the user.