Overview of the DP Base Interface
DP Base Programming Interface for CP 5613/CP 5614
44
C79000-G8976-C108-01
3.5 Fast Logic
Purpose
With the fast logic property of the CP 5613/CP 5614, you can assign parameters to
the CP so that it automatically monitors data from slaves and triggers reactions on
other slaves.
This has the following advantages:
x
The user program has less to do.
x
The data transfer is faster due to separating the functions from the PC software.
x
By being independent of the PC software, the reaction to the input signal is
guaranteed.
For the software version in which this property is available, refer to the version
table in Section in the Installation Instructions.
Procedure
Your program can activate functions that assign parameters for fast logic
(DP_fast_logic_on) or clear parameters again (DP_fast_logic_off).