Description
The basic XLS control unit consists of the following
subassemblies: PMI Person Machine Interface; PSC-12
Power Supply; DLC Device Loop Card; ZIC-4A Zone
Indicating Card; CC-5 Card cage; ID-SP Inner Door Blank
Single Plate; CAB-1, CAB-2 or CAB-3 enclosures. Op-
tional modules that can be installed with the XLS System
include: CC-2 Card Cage; NIC-C Network Interface Card;
ZIC-8B/ZIC-2C Zone Indicating Card 8 circuits; CRC-6
Control Relay Card; OCM-16 Output Control Module;
SCM-8 Switch Control Module; LCM-8 LED Control
Module; FCM-6 Fan Control Module; SIM-16 Supervised
Input Module; PSX-12 Power Supply Extender; RNI Re-
mote Network Interface; RPM Remote Printer Module;
SSD System Status Display; MDACT Multi-Point Digital
Alarm Communicator; REMBOX2 Two Module Remote
Enclosure; REMBOX4 Four Module Remote Enclosure.
The XLS panel is compatible with a full line of intelligent
initiating devices highlighted by the FirePrint Application
Specified Detectors, models HFP-11 and HFPT-11. It is also
compatible with the NCC series of graphics command
centers.
PMI Person Machine Interface
The Person Machine Interface is the heart of the FireFinder-
XLS system. The PMI serves as both operator interface
and central microprocessor for the system. From the PMI
the user can acknowledge events, control the system
notification appliance circuits and reset the system.
Detailed information about the nature and location of the
events can also be displayed.
The PMI contains the site-specific program configuration -
created in the Zeus tool. The controller in the PMI provides
all system logic and supervision.
The PMI contains a large 6" (1/4 VGA) monochrome LCD
display, touch screen and LED's for displaying system
status. An audible sounds when there are unacknowledged
events on the PMI. The display is surrounded by keys that
are used to control the displayed information and to
navigate through these screens. Keys are also provided to
obtain "Help" and to enter into the menu features of the
PMI.
The FireFinder system is controlled and operated from the
PMI. The intuitive person machine interface uses large
lighted buttons to prompt users as to the next correct
system operation that is available (Acknowledge, Silence,
Unsilence Audible or Reset).
DLC Device Loop Card
The DLC Device Loop Card is the interface for connection
with FireFinder XLS detectors and initiating devices
including manual stations, control and input devices. The
DLC plugs into one slot of the CC-2 or CC-5 card cage.
Programming the DLC is accomplished using the
FireFinder XLS Zeus configuration tool. The DLC takes one
address on the network and communicates with two
device circuits with a total of up to 252 detectors and
devices. The DLC has 12 LEDs for diagnostic purposes
and provides ground fault detection and zone isolation
circuitry.
ZIC-4A Zone Indicating Card
The Zone Indicating Card ZIC-4A provides four fully super-
vised programmable output circuits for use on the
FireFinder XLS Fire Alarm Control Panel. The ZIC-4A
supplies four Class B (Style Y) or Class A (Style Z) type
output circuits, power limited to 4.0 amps maximum per
circuit. Each circuit can be independently programmed for
use with listed audible or visual notification appliances,
listed emergency audio speakers, municipal tie boxes,
leased lines, or as releasing circuits. The ZIC-4A plugs into
one slot in the CC-5 or CC-2 Card Cage, and has on-board
LEDs for system status and troubleshooting. Indication of
power, communication, internal operation, and ground fault
conditions are provided, as well as indication of circuit
activation or trouble conditions.
DLC Device Loop Card
PMI Person Machine Interface
ZIC-4A Zone Indicating Card