ZIC-8B/ZIC-2C
The Zone Indicating Card ZIC-8B provides eight fully
supervised programmable output circuits for use on the
FireFinder XLS Fire Alarm Control Panel. The ZIC-8B
supplies 8 Class B (Style Y) type output circuits, power
limited to 2.0 amps maximum per circuit. Each circuit can
be independently programmed for use with listed audible
or visual notification appliances, or listed emergency audio
speakers. The ZIC-8B plugs into one slot in the CC-5 or
CC-2 Card Cage, and has on-board LEDs for system status
and troubleshooting. The ZIC-2C mounts directly on the
ZIC-8B, and allows each of the ZIC-8B output circuits to be
used for 2-channel voice applications. Indication of power,
communication, internal operation, and ground fault
conditions are provided, as well as indication of circuit
activation or trouble conditions.
ZIC-8B/ZIC-2C
NIC-C
NIC-C
The Model NIC-C Network Interface Card provides HNET or
XNET network communications between enclosures. In
addition to the HNET or XNET communication the NIC-C
provides CAN network communication within an enclosure
or external to the enclosure. The HNET or XNET can be
wired Style 4 or Style 7. The CAN network can be wired
Style 4 only.
When the NIC-C is used for HNET communications it
provides communication between enclosures on a single
system.
When the NIC-C is used for XNET communications it
provides communication between systems. The maxi-
mum of XNET NIC-Cs on a single system (single node) is
one, for a total of 64 XNET NIC-Cs on a Peer-To-Peer
Networked System.
The NIC-C Card has diagnostic LEDs that indicate Card Fail,
CAN Fail, HNET Fail, XNET Fail, Ground Fault, Loop A Fail
and Loop B Fail, as well as LEDs to indicate Power, Style
and Active Networks.
HLIM Line Isolator Module
HLIM Line Isolator Module
The HLIM loop isolator module provides short circuit
protection on FireFinder XLS intelligent device circuits
(DLC). When a short is detected by the HLIM, it isolates
the affected segment of the circuit, allowing the remaining
devices to continue operation. The HLIM is self-restoring,
automatically reconnecting to circuit segment when the
fault is removed.
It can be wired in either a Style 4 or Style 6 configuration.
The HLIM does not occupy a device address on the DLC
circuit and requires no programming. Up to fifteen HLIMs
may be installed on each DLC loop.
HCP
HCP
The HCP provides an intelligent control point for the
FireFinder XLS Control Panel. The HCP can be
programmed as an independent, remotely located tele-
phone zone, speaker zone or notification appliance circuit.
The HCP is designed to be used with the Siemens Fire
Safety notification appliance product line.
The HCP communicates through the DLC analog loop and
can be wired either Class A (Style Z) or Class B (Style Y).
The 24 VDC power input comes from either the control
panel or from any UL listed power limited, auxiliary power
supply.