For internal use only
Siemens Industry, Inc.
Building Technologies Division Delivery Release
Fire Safety & Security Products
Product Line: Fire Detection
Date: 2013-June– 14
Distribution (please mark):
Product
Solution Multi-channel
Author: Bruce Jankowitz
Siemens Industry, Inc.
Building Technologies Division
Fire Safety & Security Products
8 Fernwood Road
Florham Park, NJ 07932 {U.S.A.}
Page: 5 / 8 PLN Number: DR 08-14 XLS MP9
The FDCIO422 four-input, four-output module is also supported with FireFinder XLS 9.0. The input can be
configured for four Class B inputs, or two Class A inputs. Each input is separately configurable as alarm, security,
supervisory, waterflow, Carbon Monoxide, trouble, or other event types.
All detector features are configured in Zeus Rev. 9.02.0015, and require DLC Rev. 06.00.0008. Support for the
Cerberus detection devices is currently limited to systems using the PMI-2 at rev 9.02.0019.
Support for the SBGA-34 Audible Base
The SBGA-34 Audible Base is supported by XLS 9.0. These bases can now be used with the new Cerberus detection
devices. The base includes jumper settings to select steady, Temporal 3 or Temporal 4 (carbon monoxide signal)
sound patterns when activated. If the base is configured for steady and gets its power from a Notification
Appliance Circuit, the NAC can be coded, and this coded signal can be sounded at the base upon activation. This
offers the ability to synchronize audible signal patterns between multiple bases and/or bases and standard horns.
Additionally, since XLS supports multiple audible patterns by event and priority, these bases can now play different
patterns based on different event logic. The SBGA-34 audible base is compatible with the Cerberus and the H-
Series detectors.
Support for Temporal 4 Coded Audible for Carbon Monoxide events
NFPA 720 is the standard for carbon monoxide life safety systems. This standard specifically requires a different
audible pattern called Temporal 4 to indicate carbon monoxide life safety events. Since FireFinder XLS now
supports carbon monoxide life safety events through the dual optical thermal multi-criteria detector with CO
sensor, it also now supports the Temporal 4 audible code on ZIC-4A and ZIC-8B cards. The use of Temporal 4 on
NACs for FireFinder XLS requires Zeus Rev. 9.02.0015, PMI Rev 9.02.0019, ZIC-4A Rev.08.00.0000, and ZIC-8 Rev.
04.00.0000. Since HTRI input modules can now be configured as carbon monoxide events, the Temporal 4 feature
is supported on systems using either PMI or PMI-2 operating units.
Certifications
All the features and modules described in this document are UL Listed, ULC Listed, CSFM Approved, FDNY and
OSHPD Approved.
PMI2 approvals
UL864 9th Edition Listed
UL2572 Listed
ULC S527-99 Listed
FM Approved