Chapter 10. Configuring the I/O Driver from FIX/iFIX Applications187
See Also
Specifying Signal Conditioning in Database Manager
S5CO Signal Conditioning
Signal conditioning defines how the process database scales incoming data. S5CO
signal conditioning converts an S5 counter value into an integer from 0 to 8191.
Parameters for S5CO Signal Conditioning
Write
Algorithm
Writes to an S5 Time register after
converting a 3BCD value, using the
following algorithm:
Result =
(InputData/Time_Resolution)
Write
Algorithm
Variables
InputData – the database block’s
current value.
Time_Resolution – the value stored
in bits 13 and 12 of the register
converted as follows:
00 – yields a resolution of 0.01
01 – yields a resolution of 0.1
10 – yields a resolution of 1
11 – yields a resolution of 10
Result – the value sent to the process
hardware.
Description S5 Counters to integers.
Input Range 0 to 8191.
Scaling No Scaling.