Representation of analog values
C.2 Representation of analog values in voltage measuring ranges
Analog Input Module AI 8xU/I HS (6ES7531-7NF10-0AB0)
46 Manual, 07/2014, A5E03484886-AC
C.2
Representation of analog values in voltage measuring ranges
The following tables list the decimal and hexadecimal values (codes) of the possible voltage
measuring ranges.
Table C- 4 Voltage measuring range ±10 V and ±5 V
Values
Voltage measuring range
Range
dec
hex
±10 V
±5 V
32767
7FFF
>11.759 V
>5.879 V
Overflow
32511
7EFF
11.759 V
5.879 V
Overshoot range
27649
6C01
27648
6C00
10 V
5 V
Rated range
20736
5100
7.5 V
3.75 V
1
1
361.7 µV
180.8 µV
0
0
0 V
0 V
-1
FFFF
-20736
AF00
-7.5 V
-3.75 V
-27648
9400
-10 V
-5 V
-27649
93FF
Undershoot range
-32512
8100
-11.759 V
-5.879 V
-32768
8000
< -11.759 V
< -5.879 V
Underflow
Table C- 5 Voltage measuring range 1 to 5 V
Values
Voltage measuring range
Range
dec
hex
1 to 5 V
32767
7FFF
>5.704 V
Overflow
32511
7EFF
5.704 V
Overshoot range
27649
6C01
27648 6C00 5 V Rated range
20736
5100
4 V
1
1
1 V + 144.7 µV
0
0
1 V
-1
FFFF
Undershoot range
-4864
ED00
0.296 V
-32768
8000
< 0.296 V
Underflow