Siemens HS Dokumentacja Strona 49

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 61
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 48
Representation of analog values
C.4 Measured values for wire break diagnostic
Analog Input Module AI 8xU/I HS (6ES7531-7NF10-0AB0)
48 Manual, 07/2014, A5E03484886-AC
C.4
Measured values for wire break diagnostic
Measured values on diagnostic event "wire break", dependent on diagnostics enables
Error events initiate a diagnostics entry and trigger a diagnostics interrupt if configured
accordingly.
Table C- 8 Measured values for wire break diagnostic
Format
Parameter assignment
Measured values
Explanation
S7
"Wire break" diagnostics enabled
"Overflow/Underflow" diagnostics
enabled or disabled
("Wire break" diagnostics takes priority
over "Overflow/Underflow" diagnostics)
32767 7FFF
H
"Wire break" or "Open circuit" diagnostic
alarm
"Wire break" diagnostics disabled
"Overflow/Underflow" diagnostics
enabled
-32767 8000
H
Measured value after leaving the under-
shoot range
Diagnostic alarm "Low limit violated"
"Wire break" diagnostics disabled
"Overflow/Underflow" diagnostics
disabled
-32767 8000
H
Measured value after leaving the undershoot
range
Przeglądanie stron 48
1 2 ... 44 45 46 47 48 49 50 51 52 53 54 ... 60 61

Komentarze do niniejszej Instrukcji

Brak uwag