Siemens EA 726 Series Instrukcja Użytkownika Strona 7

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 8
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 6
17
Network module (SAFEDLINK)
FN2001-A1
For networking various stations
18
Repeater (SAFEDLINK)
FN2002-A1
For the extension of the system bus C-WEB, max. 1 between 2 sta-
tions (mounting direct onto plane surface, onto a U-rail TS35 or in
housings FDCH221)
19
Sounder module
FCA2005-A1
For split-up of 1 to 4 conventional horn lines
20
Battery (12 V, 17 Ah, VDS)
FA2005-A1
For emergency power supply
Battery (12 V, 26 Ah, VDS)
FA2006-A1
Battery (12 V, 45 Ah, VDS)
FA2007-A1
21
Fire brigade periphery module
FCI2001-D1
For Germany (FBF, FSD, ÜE, FSE, ÖA, KL)
22
19" mounting kit
FHA2016-A1
For the installation in 3
rd
party housings
23
License key Sx
FCA20xx
For special functions
24
Cable kit (communication)
FCA2014-A1
For flexible cable connections to the modules on the operating unit
25
Power supply kit (150 W, B)
FP2005-A1
For additional power supply
26
I/O card
FCI2008-A1
12 programmable inputs/outputs
27
Relay module
Z3B171
Space for U-rail TS35 L=70 mm (on site) for max. 4 relay modules
Technical data
Mains voltage
AC 98…127 V / AC 196…253 V
Power supply
150 W
Operating voltage
DC 21…28.6 V
Operating current
max. 5 A
Battery capacity
2 x 12 V, 45 Ah
Battery monitoring / mains monitoring
yes / yes
Connectable detector series
Cerberus PRO FD720 (C-NET)
Number of C-NET addresses
max. 1512
Number of lines
Loops with loop extension
stub lines
4 / 8
8 / 16
C-NET (4 per line card)
max. 20
Integrated inputs/outputs
Relay output
Remote transmission alarm / fault
Monitored outputs
Alarm / Fault / Horn
Free programmable inputs/outputs
1 / 1
1 / 1 / 2
12
Free programmable inputs/outputs with max. 5 extra I/O cards
60 (12 per card)
Operating unit
integrated
Plug-in position for RS232, RS485 serial ports
2
Plug-in position for network modules
2
Plug-in position for loop extension
2
Slots for line cards (on fitted card cage)
max. 5
Mounting spaces for cable kit (communication)
2
Sounder module
max. 2
Ethernet connection RJ45
1
Operating temperature
-8…+42 °C
Storage temperature
-20…+ 60 °C
Humidity (no condensation permitted)
95 % rel.
Dimensions (W x H x D)
Without cover cap
With Cover cap
430 x 796 x 260 mm
430 x 796 x 288 mm
Color
Housing
Cover cap
grey, ~RAL 7035
grey, ~RAL 000 50 00
Protection category (IEC 60529)
IP30
Standards
EN 54-2, EN 54-4
Approvals
VdS
LPCB
FM
G210084
126bn/08
approved
7
Building Technologies
CPS Fire Safety
Przeglądanie stron 6
1 2 3 4 5 6 7 8

Komentarze do niniejszej Instrukcji