Control via the Operator Panel 04/04
SINAMICS G130 - Operator Panel AOP30
5-18 Operating Manual
The following image shows how the entries are assigned to the screen positions:
OPERATION 12:25:30 S
Entry 01 Entry 02
Entry 03 Entry 04
Entry 05 Entry 06
Entry 07 Entry 08
Entry 09 Entry 10
OPERATION 12:25:30 S
Entry 01 Entry 02
Entry 03 Entry 04
Entry 05 Entry 06
Entry 09
0% 50% 100%
Entry 07 Entry 08
OPERATION 12:25:30 S
Entry 01 Entry 02
Entry 03 Entry 04
Entry 05
0% 50% 100%
Entry 06
0% 50% 100%
OPERATION 12:25:30 S
Entry 01
0% 50% 100%
Entry 02
0% 50% 100%
Entry 03
0% 50% 100%
Fig. 5-4 Position of the entries in the operation screen
Lists of Signals for the Operation Screen
Vector Object
Table 5-1 List of signals for the operation screen –vector object
Signal Parameters Short name Unit Scaling
(100 % = ...), see Table
5-2
Factory setting (entry no.)
Speed setpoint upstream of ramp-function
generator (1)
r1114 NSETP 1/min p2000
Output frequency (2) r0024 F_OUT Hz Reference frequency
Power smoothed (3) r0032 P_ACT kW r2004
DC link voltage smoothed (4) r0026 UDC V p2001
Actual speed smoothed (5) r0021 N_ACT 1/min p2000
Absolute actual current smoothed (6) r0027 I_IST A p2002
Motor temperature (7) r0035
1
T_MOT °C Reference temperature
Converter temperature (8) r0037 T_LT °C Reference temperature
Actual torque smoothed (9) r0031 M_ACT Nm p2003
Converter output voltage smoothed (10) r0025 C_OUT V p2001
For diagnostic purposes
Speed setpoint smoothed r0020 NSETP 1/min p2000
Control factor smoothed r0028 % Reference control factor
1
If a temperature sensor has not been installed, a value of –200°C is displayed.