1-4
Allowable values:
*Voltage…………………….…10% of nominal supply
voltage.
*Frequency……………………50/60 Hz 1 Hz.
*Momentary power failure…....Less than 10 msec.
*Voltage impulse……………...Leak value is 200% or less of
the effective value (rms value)
of the line voltage with pulse
duration of 1.5 msec.
*Waveform distortion…………7% or less
*Imbalance in line voltages……5% or less
Grounding:
(1) The machine must be grounded independently of other
machines.
(2) If electric welders or electric discharge machines are
grounded to the frame of the plant building, do not
connect the ground wire of the machine to the plant
frame.
(3) The ground wire must be as short as possible and have the
same diameter as the input power cable.
Class 3 ground
Grounding resistance: 100or less
(4) Please measures the ground wire to earth, exactly.
The grounding resistance must be less than 100with the
single device.