UM344-2 APPENDIX A - FUNCTION BLOCK DESCRIPTIONS
September 1995
The gain for this controller is fixed at a value of 1.00. While the displayed gain can be changed, it will not
affect the controller.
Equations
GE + F
O =
TIs + 1
AUTO when output O is connected to feedback F
TDs 1
O = +/-PG[P(1+ )-S] + [ ]
(TD/DG)s + 1 TIs
MANUAL O = F
A.9 FUNCTION BLOCK SUMMARY
SENSOR INPUT BLOCK
- Input Type
MV (Millivolts)..........................................Wide or Narrow
RTD.........................................................PT100 ohm DIN & US, PT200 ohm DIN & US, PT500
ohm DIN & US
T/C...........................................................J, K, E, T, R, S, B, N
Ohm .........................................................Wide or Narrow
- MV Units.......................................................Celsius, Fahrenheit, Rankine, Kelvin, MV, Ohms
- MV Range.....................................................LO and HI range values
- Damping........................................................0 to 120 seconds
- Burnout Direction...........................................Upscale or Downscale
OPERATOR DISPLAY BLOCK
- Local Display Code ........................................Percent, Process Variable, Measured Variable
Block Diagram, ID Controller
PV
TDs
TD
DG
s + 1
+
+
+
+
+ / -
+ / -
SP
GE
s + 1TI
1 Output
F
X02880S0