INSTALLATION UM344-2
September 1995
4
-
8
4.3.4 Power Supply Requirements
A power supply is needed to power the Transmitter(s). The power supply can be:
Ÿ A separate stand-alone supply capable of powering several Transmitters. It can be mounted in a
control room or in the field. Follow the power supply manufacturer's recommendations with regard to
mounting and environmental considerations.
Ÿ Located in a controller (such as a Primary Master) or other station able to safely provide additional
operating current and meet the power supply specifications of Section 8.3.2.
Determine needed power supply output voltage by calculating the Network Resistance and consulting
Figure 4-4. It shows the minimum power supply voltage needed for the calculated Network Resistance.
The total Network Resistance is the sum of the Current Sense Resistance, end-to-end Barrier Resistance
(if used), wire resistance, and any other resistances in the loop. The minimum Network Resistance (see
Glossary) required to support HART communications is 250. The maximum resistance is 1100.
FIGURE 4-4 Supply Voltage Versus Network Resistance
1650
1200
1100
1000
800
600
500
250
0
10V
12V
17V 20V 24V
30V 34V 40V
45V0
X02817S1
42V
Minimum Power Supply Voltage (VDC)
Network Resistance (OHMS)
OPERATING
REGION