INITIAL TRANSMITTER SET-UP UM344-2
September 1995
3
-
8
3.3.3 Loop Testing
Testing the loop involves making sure that the
Transmitter is sending out the proper current signal and
that the other elements in the loop are receiving this
signal. The Loop Override mode is used to test the loop.
1. At the On-Line Menu, press LOOP OVRD. The
adjacent screen will be displayed. Press CONT and
then PROCEED.
2. Choose either 4 mA or 20 mA from the menu, or
choose OTHR to enter another value. After a value
is entered, the Transmitter will output the value
chosen. Read the analog current value on a:
Ÿ Recorder or control station in the loop
Ÿ Milliammeter connected in series in the loop
Ÿ Milliammeter connected to the TEST terminals
(Figures 3-1 and 3-2)
Ÿ Analog Voltage may be read on a voltmeter
connected across the sense resistor.
NOTE
This is intended as a functional test. To
check calibration accuracy a DMM of at
least .05% accuracy must be used.
If the transmitter is not working properly, try to
recalibrate it (see Section 6.1).
3.4 REVIEW CONFIGURATION
DATA
Before placing the Transmitter on-line, check that the
proper configuration information has been stored.
1. Establish communication between the Transmitter
and MXC.
2. Using the MXC screens, compare the uploaded
configuration with user's configuration
documentation.
LOOP OVERRIDE SETS
TRANSMITTER OUTPUT
TO ENTER-
ED VALUE END CONT
WARNING! SELF TEST
MAY BUMP TRANSMITTER
OUTPUT A-
BORT CONT
LOOP OVERRIDE - CHOOSE
CURRENT OUTPUT LEVEL
4 MA 20 MA OTHR END
Dev ID: 210300003C
Tag: TTC-101 ADD: 00
LOOP CAL/ CON -
END
OVRD
TEST FIG