Application description
Connecting CU230P-2 DP to the PROFIBUS DP network
Commissioning of the Control Unit CU230P-2 DP with PROFIBUS ID-No: 35934076
Version 1 Issue May 2009 10/33
Copyright © Siemens AG 2009 All rights reserved
PDF_Commissioning_of_CU230P_2_DP_with Profibus_en_V1.doc
2.4 Setting the PROFIBUS DP address
Before the PROFIBUS DP interface is used, the address of the node point
(inverter) must be set.
The following methods are available for setting the PROFIBUS DP address:
• Using the address switch on the Control Unit
• Using parameter p0918
Note
Important notes for setting the PROFIBUS address
The address setting on the DIP switch takes priority over the p0918
settings.
The PROFIBUS DP address can only be set using p0918 when the
address 0 is set on the DIP switches of the Control Unit (factory setting).
When the address switch is set to a value ≠ 0, the setting in p0918 is
ignored.
The valid address range for Siemens controllers is 1 to 125. Addresses 126
and 127 cannot be used with SIMATIC controllers.