Application description
Connecting CU230P-2 DP to the PROFIBUS DP network
Commissioning of the Control Unit CU230P-2 DP with PROFIBUS ID-No: 35934076
Version 1 Issue May 2009 12/33
Copyright © Siemens AG 2009 All rights reserved
PDF_Commissioning_of_CU230P_2_DP_with Profibus_en_V1.doc
2.5 Communication settings for PROFIBUS DP
PROFIBUS DP parameters
You can fully integrate your inverter with a CU230P-2 DP Control Unit into
a PROFIBUS communication system without the need for any PROFIBUS-
specific parameter settings when the following preconditions are met:
The PROFIBUS address is set using a DIP switch
The communication procedure uses standard telegram 1
If you want to modify the communication settings, the parameters that you
can use to make changes are listed in the table below.
Table 2-2 PROFIBUS DP parameters
Parameter Description
P0918 PROFIBUS address
P0922 Selection of the PROFIBUS standard telegram
P2038
Selection of the communication profile (PROFIdrive profile 4.1 /
VIK NAMUR)
P2042
Selection of the profile code for the controller (PROFIdrive profile
4.1 / VIK NAMUR)
r2050 Set-point source for process data (BICO)
P2051 Actual values for process data (BICO)
P2030 Fieldbus interface telegram selection
P2037 PROFIdrive processing mode
P2040 Fieldbus telegram off time
P2044 PROFIdrive fault delay for setpoint
P2047 PROFIBUS additional monitoring time
r2054 Diagnostics of the communication module
r2055 PROFIBUS diagnostics - standard
r2075 PROFIdrive diagnostics telegram offset
P2079 PROFIdrive PZD extended telegram selection