Appendix E: Device Data Format
124 Siemens Energy & Automation, Inc.
E.19 Device Type: 7SJ600
Real-Time Device Data Stored in PLC (7SJ600)
Function Register Location in
PLC Block
1
Range or Contents
Phase A current (IL1) 0 %
Phase B current (IL2) 1 %
Phase C current (IL3) 2 %
Operating Temperature (Theta) 3 %
Binary Inputs 1-3 4 Refer to Section 5.8
Signal Relays and Trip Relays 5 Refer to Section 5.8
LED Indicators 1-4 6 Refer to Section 5.8
General Status Word 1:
2
7 Bit Contents
15 >Overcurrent protection: blockstage IE>> (Valid)
14 >Overcurrent protection: blockstage IE>> (Status)
13 >Overcurrent protection: blockstage Ip (Valid)
12 >Overcurrent protection: blockstage Ip (Status)
11 >Overcurrent protection: blockstage I> (Valid)
10 >Overcurrent protection: blockstage I> (Status)
9 >Overcurrent protection: blockstage I>> (Valid)
8 >Overcurrent protection: blockstage I>> (Status)
7 Thermal overload prot.: Thermal warning (Valid)
6 Thermal overload prot.: Thermal warning (Status)
5 Thermal overload protection is active (Valid)
4 Thermal overload protection is active (Status)
3 >Circuit breaker closed (Valid)
2 >Circuit breaker closed (Status)
1 Any protection operative (Valid)
0 Any protection operative (Status)
General Status Word 2:
2
8 Bit Contents
15 AR: Auto-reclose in progress (Valid)
14 AR: Auto-reclose in progress (Status)
13 AR: Auto reclosure is active (Valid)
12 AR: Auto reclosure is active (Status)
11 O/C fault detection earth (Valid)
10 O/C fault detection earth (Status)
9 O/C fault detection phase L3 (Valid)
8 O/C fault detection phase L3 (Status)
7 O/C fault detection phase L2 (Valid)
6 O/C fault detection phase L2 (Status)
5 O/C fault detection phase L1 (Valid)
4 O/C fault detection phase L1 (Status)
3 >Overcurrent protection: blockstage IEp (Valid)
2 >Overcurrent protection: blockstage IEp (Status)
1 >Overcurrent protection: blockstage IE> (Valid)
0 >Overcurrent protection: blockstage IE> (Status)
General Status Word 3:
2
9 Bit Contents
15 >Trip circuit supervision: CB aux. (Valid)
14 >Trip circuit supervision: CB aux. (Status)
13 >Trip circuit supervision: Trip relay (Valid)
12 >Trip circuit supervision: Trip relay (Status)
11 Supervision of starting time active (Valid)
10 Supervision of starting time active (Status)
9 >Starting time supervision: Block stage (Valid)
8 >Starting time supervision: Block stage (Status)
7 >inst. high set prot.: Block stage I>>> (Valid)
6 >inst. high set prot.: Block stage I>>> (Status)
5 Unbalanced load protection is active (Valid)
4 Unbalanced load protection is active (Status)
3 >Reversed phase rotation (Valid)
2 >Reversed phase rotation (Status)
1 AR: Reclosure blocked (Valid)
0 AR: Reclosure blocked (Status)
Przeglądanie stron 127