5 Creating Project Files—Modbus Master to Devices
42 Siemens Energy & Automation, Inc.
The relevant status codes (Text #) are listed below.
Table 5.1 7SJ600 Relay Information
For Requesting Status of the 7SJ600 Relay’s Three Binary Inputs
Text Number/Status Code
(default value returned if
not converted)
Description of Returned Binary
Input Status Codes: I1
indicates Input 1; I2,3 indicates
Inputs 2 and 3
Suggested Value (Using This Conversion Table)
Value
Inputs I3 I2 I1
00 000
1342 I1,2 Inactive : I3 Active 4 0 1 0 0
1343 I1,3 Inactive : I2 Active 2 0 0 1 0
1344 I1 Inactive : I2,3 Active 6 0 1 1 0
1345 I2,3 Inactive : I1 Active 1 0 0 0 1
1346 I2 Inactive : I1,3 Active 5 0 1 0 1
1347 I3 Inactive : I1,2 Active 3 0 0 1 1
1348 I1,2,3 Active 7 0 1 1 1
For Requesting Status of the 7SJ600 Relay’s Two Trip Contacts and Two Signal Contacts
Text Number/Status Code
(default value returned if
not converted)
Description of Returned Trip
and Signal Relay Status
Codes: S1,2 indicates Signal
Relays 1 and 2; T1,2 indicates
Trip Relays 1 and 2
Suggested Value (Using This Conversion Table)
Value
Outputs S2S1T2T1
Bits 15 . . . 43210
1349 S1,2 T1,2 Open 0 0 0000
1350 S1,2 T1 Open : T2 Closed 2 0 0010
1351 S1,2 T2 open : T1 Closed 1 0 0001
1352 S1,2 Open : T1,2 Closed 3 0 0011
1353 S1 T1,2 Open : S2 Closed 8 0 1000
1354 S1 T1 Open : S2 T2 Closed 10 0 1010
1355 S1 T2 Open : S2 T1 Closed 9 0 1001
1356 S1 Open : S2 T1,2 Closed 11 0 1011
1357 S2 T1,2 Open : S1 Closed 4 0 0100
1358 S2 T1 Open : S1 T2 Closed 6 0 0110
1359 S2 T2 Open : S1 T1 Closed 5 0 0101
1360 S2 Open : S1 T1,2 Closed 7 0 0111
1361 T1,2 Open : S1,2 Closed 12 0 1100
1362 T1 Open : S1,2 T2 Closed 14 0 1110
1363 T2 Open : S1,2 T1 Closed 13 0 1101
1364 S1,2 T1,2 Closed 15 0 1111
For Requesting Status of the 7SJ600 Relay’s Four Programmable LEDs
Text Number/Status Code
(default value returned if
not converted)
Description of Returned LED
Status Codes: L1,2 indicates
LEDs 1 and 2
Suggested Value (Using This Conversion Table)
Value
Outputs L4L3L2L1
Bits 15 . . . 43210
1365 L1,2,3,4 Off 0 0 0000
1366 L4 On : L1,2,3 Off 8 0 1000
1367 L3 On : L1,2,4 Off 4 0 0100
1368 L3,4 On : L1,2 Off 12 0 1100
1369 L2 On : L1,3,4 Off 2 0 0010
1370 L2,4 On : L1,3 Off 10 0 1010
1371 L2,3 On : L1,4 Off 6 0 0110