Appendix B: Supported Devices
62 Siemens Energy & Automation, Inc.
BSupported Devices
The following Siemens ACCESS devices are sup-
ported by the DTU3005B.
In addition, the following Siemens protective relays
and measuring transducers using the VDEW protocol
can be connected using the DTU3005B. This device is
designed for use with DIGSI Configuration software.
SEAbus port expander mode is not supported for this
device.
B.1 Application Notes—
Communication Port Settings for
7-Series Protective Relays
The following are the required settings in the relays
for communications.
All relays (except 7SJ600)
7SJ600
Table B.1 Supported Siemens Devices
Device
4720 Power Meter
4700 Power Meter
4300 Power Meter
Static Trip III Trip Unit
SAMMS-MV Motor Protection Device
SAMMS-LV Motor Protection Device
ISGS Intelligent SwitchGear System Protective Relay
S7-I/O Addressable Relay
Sentron SB Energy Communicating Trip Unit
Table B.2 Supported Siemens Protective Relays and
Measuring Transducers
Device
7SA511 Feeder Protection Relay
7SA513 EHV Line Protection Relay
7SD511 Current Comparison Protection Relay
7SD512 Current Comparison Protection Relay
7SJ511 Overcurrent Protection Relay
7SJ512 Feeder Protection Relay
7SJ531 Line and Motor Protection Relay
7SJ600 Overcurrent Protection Relay
7UT512 Differential Protection Relay
7UT513 Differential Protection Relay
7KG6000 (SIMEAS T) Measuring Transducer
Table B.3 7200 Rear Port Settings
Menu
Number
Menu Setting
7201 Device
Address
Set to a unique address to be
used in the DTU.
7208 Function Type This must be left at its default
value of "176".
7221 Rear Port Par-
ity
Set this to 8N1, 8 data bits, no
parity, and 1 stop bit.
7222 Rear Format Set this to "VDEW Extension".
7225 Rear Baud Set this to match the baud rate
of the configuration in the
DTU.
Table B.4 72 Port Settings
Menu Setting
DEVICE Set to a unique address, between 1
and 254, which will be used in the
DTU.
F-TYPE This should be left at its default value
of "160".
PC-INT Data format of this interface should be
set to "DIGSI V3".
BAUD Set this to match the baud rate of the
configuration in the DTU.
PARITY Set this to 8N1, 8 data bits, no parity,
and 1 stop bit.