Installing and connecting the device
3.2 Preparing for installation
Industrial Thin Client ITC1200, ITC1500, ITC1900, ITC2200
Operating Instructions, 04/2013, A5E03474888-02
23
Degrees of protection
The degrees of protection of the HMI device can only be guaranteed if the following
requirements are met:
Material thickness at the mounting cutout for IP65 degree of protection or Front face only
Type 4X/Type 12 (indoor use only): 2 mm to 6 mm
Permitted deviation from plane at the mounting cutout: ≤ 0.5 mm
This condition must be fulfilled for the mounted HMI device.
Permissible surface roughness in the area of the seal: ≤ 120 µm (R
z
120)
Compatibility of the mounting cutout to other HMI devices
The mounting cutouts of all devices with widescreen display of comparable display size are
compatible.
Keep in mind that even though the dimensions of the mounting cutout are identical, the
device depth and/or enclosure front dimensions may differ from the corresponding
dimensions of the predecessor devices and other widescreen displays.
Dimensions of the mounting cutout
+1
0
+1
0
wh
,7&  
,7&  
,7&  
,7&  
w
h