Configuration Examples
6-26
SIMATIC 505 PROFIBUS-FMS CP User Manual
Example of a Send-Receive Job (continued)
Figure 6-18
shows the sequence of events for a successful FDL transaction.
WY5.3
t0 t2
WX1.3
t1 t3
t4
SEND
RECEIVE
t6
t5
WX3.3
t8
WY7.3
t7
Figure 6-18
Successful T
iming Example
The list below explains the sequence of events.
t0
Send Job RLL requests that data transfer be invoked.
t1
Send Job Active bit is set by the FMS CP
. Data transfer begins.
t2
Send Job Start Bit is reset to inactive by Send job RLL in response to
Job Active bit going high.
t3
Send job completes the data transfer. Send job resets Job Active bit.
Send job is complete.
t4
Receive job RLL requests that received data be processed and stored.
t5
Receive Job Active bit is set by the FMS CP module. FMS CP begins
storage of received data.
t6
Receive Job Start Bit is reset to inactive by Receive job RLL in response
to Job Active bit going high.
t7
Receive job has stored received data in programmable logic controller
memory
. Receive job resets Job Active bit. Receive job is complete and
stores job status of 0 (successful transaction).
t8
Send job re-enables the data transfer for another data transfer if
required.
Successful T
iming
Example