Using the COM5434 Configurator
5-13
SIMATIC 505 PROFIBUS-FMS CP User Manual
5.4 Defining the Module Local Configuration
The
module local configuration, shown in Figure 5-8, identifies the local
station address where the FMS CP module resides and defines the
communication parameters used by the FMS network. Y
ou cannot configure
connections or communication services for an FMS CP module unless you
define the local configuration for that module.
✂
File Edit Transfer Options Diagnostics Help
Untitled
– COM5434
This
module’
s FMS PROFIBUS communication parameters
FMS Connections
FDL Connections
Communication Jobs
FMS Jobs
Send-Receive Jobs
FMS Data T
ypes
FMS
FDL
FMS
P–P
S–R
DTs
Peerlink II Services
FMS V
ariables
<no description>
Module Local Configuration
Local Station Address:
Slot T
ime (T
slot):
Max. Sta. Delay (Max_T
sdr):
300
150
4
Highest Station Address:
126
Bus Parameter Profile:
Standard
Baud Rate:
1.5 MBaud
# of Masters (holds token):
2
# of Slaves (no token):
0
Min. Sta. Delay (Min_T
sdr):
Setup Time (T
set):
11
1
Quiet T
ime (Tqui):
Gap Factor:
0
10
Retry Limit:
T
oken Rotation (Ttr):
1
9900
Click here.
Figure 5-8 Module
Local Configuration
T
o define the module local configuration, follow the steps below:
1.
Click on
Module Local Configuration
on the configuration tree.
2.
Fill in the following fields in the input pane:
Local Station Address Enter
the local station address, within a range of
0 to 126, (PROFIBUS network address) where the FMS CP module
resides.
What Is the
Module Local
Configuration?
Defining the
Module Local
Configuration