Installing the Module
2-8
SIMATIC 505 PROFIBUS-FMS CP User Manual
2.6 Powering Up the Base
Refer
to the system manual for your programmable logic controller for
information on installing and wiring the power supply in the base. Follow
all installation guidelines and safety precautions described in your system
manual before powering up the system.
!
WARNING
Electrical
shock hazard is possible if you are not fully informed about safety
precautions before you wire and/or power up the base.
Failure to follow safety guidelines could result in death or serious injury to
personnel, and/or damage to equipment.
Review and comply with all warnings and proceedures in the system manual for
your base before powering up.
When
you power up the base, the FMS CP module executes a diagnostic
check. The diagnostic check takes a maximum of 30 seconds.
After powering up the base, observe the status of the LEDs on the bezel of
the FMS CP module. The status of the LEDs is shown in T
able 2-1.
NOTE:
When you power up the module for the first time, the LEDs display
as Stop W
ith Fault. This is normal because you have not yet configured the
module’
s flash memory
.
T
able 2-1
LED Status Diagnostic Chart
f
LED Indicator
f
Module
MOD GOOD
RUN STOP FAULT
Startup on flashing on off
Run on on off off
Stopping on on flashing off
Stop on off on off
Stop with Fault on off on on
Firmware Fault on off off on
Firmware Load on on on flashing
Fatal Error flashing flashing flashing flashing
Supplying
Power to
the Base
LED Status after
Power-up
Komentarze do niniejszej Instrukcji