Communication Services
4-4
SIMATIC 505 PROFIBUS-FMS CP User Manual
Overview (continued)
The
FMS CP module is registered in the I/O memory map of its controller as
a 4 word input (WX) and 4 word output (WY) Special Function (SF) module.
Y
ou must assign the starting I/O address, as described in Section 2.7, in
order for the programmable logic controller to be able to communicate with
the FMS CP module.
NOTE:
The designations WX1, 2, 3, 4 and WY5, 6, 7, 8, shown in the
COM5434 Configurator
, are relative to the actual starting address that you
assign in TISOFT or SoftShop for the slot where the FMS CP module is
installed. (See Section 2.7.) For example, if you assign 9 as the starting
address, then the programmable logic controller reads WX1, 2, 3, 4, and
WY5, 6, 7, 8 as WX9, 10, 1
1, 12 and WY13, 14, 15, 16. Of course, if you
configure the starting address as 1, the actual addresses match the relative
addresses shown in the COM5434 Configurator
.
Each bit in the first three words corresponds to a job. For example, if WX1 is
configured as the first word input and WY5 is configured as the first word
output for the module, then bit 1 in WY5 is the Job Start Bit for Job1, while
bit 1 in WX1 is the Job Active Bit for that same Job1 (see Figure 4-1).
WX1
WX2
WX3
WX4
WY5
WY6
WY7
WY8
Each
bit in word inputs 1 to 3 and word outputs 5 to 7 is associated with a job.
16-bit
words
CP
→
PLC
PLC
→
CP
Job Start
(WY5, bit 1)
Job Active
(WX1, bit 1)
1
0
1
0
Start Reset
Job
complete
Acknowledge
1 2 3 4 5 . . .
16
MSB LSB
116
Figure 4-1 Communication
between the PLC and the FMS CP Module
Communication
between the PLC
and the FMS CP
Module