Additional Information CLV61x Dual Port (PROFINET IO)
8017978 / 2014-11-20 © SICK AG · Germany · All rights reserved · Subject to change without notice 21
5.1.5 Example 2, receipt of a blocked telegram (HS mode):
Input: 16 bytes, output: 16 bytes, data telegram "CLV6xx-12345" with up to 12 bytes divided into 2 blocks
This can be done by triggering the CLV61x Dual Port, e.g. via the hardware. Only data can then be received by the PLC.
Time: 1 2/3 4
Remarks:
Time 1: The first data block "CLV6xx-1234" (the first 11 bytes) has been received and the PLC shows
ReceiveCount = 1. The ReceiveLength is 12 bytes.
Time 2: The PLC has detected the data and because it has noted that 12 bytes do not fit in the input range,
it knows that at least one more block follows. It confirms the first block by copying ReceiveCount to
ReceiveCountBack.
Time 3: The CLV61x Dual Port sends the next block "5" (just 1 byte is left) to the PLC with ReceiveCount = 2 and
ReceiveLength = 1.
Time 4: The PLC has detected the next block and confirms it by copying from ReceiveCount to
ReceiveCountBack. Transmission of the entire telegram has been completed.
The transportable data volume depends on the input range selected.
Input size minus 5 Input block size
The max. length of a data telegram is 4000 bytes divided into several blocks.