Siemens Simatic M7-400 Instrukcja Użytkownika Strona 43

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 158
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 42
SIMATIC S7-400
Central processing units
Y-link for S7-400H
6/43
Siemens ST 70 · 2013
Technical specifications (continued)
6
Isolation
Isolation checked with Isolation voltage 500 V
Degree and class of protection
IP20 Yes
Ambient conditions
Operating temperature
•Min. C
•max.
60 °C
Air pressure
Operating altitude above sea level,
max.
3 000 m
Dimensions
Width 40 mm
Height 125 mm
Depth
117 mm
Weight
Weight, approx. 360 g
6ES7 153-2BA02-0XB0 6ES7 197-1LB00-0XA0
General information
Requirements for DP master system
• Length of parameter assignment
message
244 byte
Supply voltage
Description via bus module
permissible range, lower limit (DC)
20.4 V
permissible range, upper limit (DC) 28.8 V
Interfaces
PROFIBUS DP
• Properties of the lower-level
DP master systems
- Transmission rate, max. 12 Mbit/s; 45.45 kbit/s to 12 Mbit/s
- Termination of lower-level
DP master system
Active terminating resistor
(Bus Terminator)
- Use of OLM/OBT
Yes
- Use of RS 485 repeaters, max.
9
- Number of DP slaves, max.
31; 64 when using RS 485 repeaters
or OLM/OBT
Protocols
PROFIBUS DP Yes
Interrupts/diagnostics/
status information
Status indicator No
Alarms
•Alarms No
Diagnostic messages
• Diagnostic functions Yes
Galvanic isolation
to lower-level DP master system Yes
Dimensions
Width 40 mm
Height 125 mm
Depth
130 mm
Weight
Weight, approx. 200 g
Kap_06_eng.book Seite 43 Donnerstag, 2. Mai 2013 4:16 16
© Siemens AG 2013
Przeglądanie stron 42
1 2 ... 38 39 40 41 42 43 44 45 46 47 48 ... 157 158

Komentarze do niniejszej Instrukcji

Brak uwag