SIMATIC S7-400
Central processing units
SIPLUS sync module
for connecting the CPU 41xH
6/51
Siemens ST 70 · 2013
■
Overview
• For linking the two CPUs 414-4H/417-4H in the subunits of the
S7-400H
• Can be plugged directly into the CPU
Note:
SIPLUS extreme products are based on Siemens Industry
standard products. The contents listed here were taken from the
respective standard products. SIPLUS extreme specific infor-
mation was added.
■
Technical specifications
6ES7 960-1AA04-4XA0 6ES7 960-1AB04-4XA0 6ES7 960-1AA06-7XA0 6ES7 960-1AB06-7XA0
Based on 6ES7 960-1AA04-0XA0 6ES7 960-1AB04-0XA0 6ES7 960-1AA06-0XA0 6ES7 960-1AB06-0XA0
Current consumption
from CPU, max.
210 mA 250 mA 220 mA 240 mA
Power dissipation, typ.
1.1 mW 1.3 mW 0.77 mW 0.83 mW
Extended range of environmental
conditions
•Temperatures 0 °C ... 60 °C 0 °C ... 60 °C -25 °C ... +70 °C -25 °C ... +70 °C
• Temperatures with reference to
ambient temperature, air pressure
and altitude
0 °C ... +60 °C at
1080 hPa ... 795 hPa
(-1000 m ... +2000 m)
0 °C ... +50 °C a
t 795 hPa ... 658 hPa
(+2000 m ... +3500 m)
0 °C ... +40 °C at
658 hPa ... 540 hPa
(+3500 m ... +5000 m)
0 °C ... +60 °C at
1080 hPa ... 795 hPa
(-1000 m ... +2000 m)
0 °C ... +50 °C at
795 hPa ... 658 hPa
(+2000 m ... +3500 m)
0 °C ... +40 °C at
658 hPa ... 540 hPa
(+3500 m ... +5000 m)
-25 °C ... +70 °C at
1080 hPa ... 795 hPa
(-1000 m ... +2000 m)
-25 °C ... +60 °C at
795 hPa ... 658 hPa
(+2000 m ... +3500 m)
-25 °C ... +50 °C at
658 hPa ... 540 hPa
(+3500 m ... +5000 m)
-25 °C ... +70 °C at
1080 hPa ... 795 hPa
(-1000 m ... +2000 m)
-25 °C ... +60 °C at
795 hPa ... 658 hPa
(+2000 m ... +3500 m)
-25 °C ... +50 °C at
658 hPa ... 540 hPa
(+3500 m ... +5000 m)
Relative humidity
(with condensation / maximum)
100 %,
incl. condensation/frost
(no commissioning in
bedewed state)
100 %,
incl. condensation/frost
(no commissioning in
bedewed state)
100 %,
incl. condensation/frost
(no commissioning in
bedewed state)
100 %,
incl. condensation/frost
(no commissioning in
bedewed state)
Resistance
• to biologically active substances /
compliance with EN 60721-3-3
Yes; Class 3B2 mold and
fungal spores (excluding
fauna). The supplied plug
covers must remain in
place over the unused
interfaces during operation.
Yes; Class 3B2 mold and
fungal spores (excluding
fauna). The supplied plug
covers must remain in
place over the unused
interfaces during operation.
Yes; Class 3B2 mold and
fungal spores (excluding
fauna). The supplied plug
covers must remain in
place over the unused
interfaces during operation.
Yes; Class 3B2 mold and
fungal spores (excluding
fauna). The supplied plug
covers must remain in
place over the unused
interfaces during operation.
• to chemically active substances /
compliance with EN 60721-3-3
Yes; Class 3C4 (relative
humidity < 75 %) incl. salt
spray in accordance with
EN 60068-2-52 (degree of
severity 3). The supplied
plug covers must remain in
place over the unused
interfaces during operation.
Yes; Class 3C4 (relative
humidity < 75 %) incl. salt
spray in accordance with
EN 60068-2-52 (degree of
severity 3). The supplied
plug covers must remain in
place over the unused
interfaces during operation.
Yes; Class 3C4 (relative
humidity < 75 %) incl. salt
spray in accordance with
EN 60068-2-52 (degree of
severity 3). The supplied
plug covers must remain in
place over the unused
interfaces during operation.
Yes; Class 3C4 (relative
humidity < 75 %) incl. salt
spray in accordance with
EN 60068-2-52 (degree of
severity 3). The supplied
plug covers must remain in
place over the unused
interfaces during operation.
• to mechanically active substances,
compliance with EN 60721-3-3
Yes; Class 3S4 incl. sand,
dust. The supplied plug
covers must remain in
place over the unused
interfaces during operation.
Yes; Class 3S4 incl. sand,
dust. The supplied plug
covers must remain in
place over the unused
interfaces during operation.
Yes; Class 3S4 incl. sand,
dust. The supplied plug
covers must remain in
place over the unused
interfaces during operation.
Yes; Class 3S4 incl. sand,
dust. The supplied plug
covers must remain in
place over the unused
interfaces during operation.
Dimensions
•Width 25 mm 25 mm 13 mm 13 mm
•Height
53 mm 53 mm 14 mm 14 mm
•Depth
140 mm 140 mm 58 mm 58 mm
Cable length, max.
10 m 10 km 10 m 10 km
Weight, approx. 65 g 65 g 14 g 14 g
Kap_06_eng.book Seite 51 Donnerstag, 2. Mai 2013 4:16 16
© Siemens AG 2013
Komentarze do niniejszej Instrukcji